Programming
PKG-SVP01B-EN
(On units with outside air heating reset selected)
Supply Air Temp Outside Air
Reset For Heating:
Start Temp: 10 F End Temp: 60 F
Factory Presets: Start = 10 F, End = 60 F
Possible Values: Start OA Temp = 73
End OA Temp = 74
1. Pressing the NEXT key will display the following screen.
(On units with zone air heating reset selected)
Supply Air Temp Zone
Reset For Heating:
Start Temp: 65 F End Temp: 68 F
Factory Presets: Start = 65 F, End = 68 F
Possible Values: Start OA Temp = 211
End OA Temp = 212
1. Pressing the NEXT key will display the following screen.
(On units with outside air heating selected)
Supply Air Temp OA Reset For Heating:
Maximum Amount of Reset Applied: 10 F
Possible Values: SAT Temp = Zone, OA
Zone Reset = 75
OA Reset = 75
1. Pressing the NEXT key will display the following screen.
(On units with outside air heating selected)
Supply Air Temp ZONE Reset For Heating:
Maximum Amount of Reset Applied: 10 F
Possible Values: SAT Temp = Zone, OA
Zone Reset = 75
OA Reset = 75
1. Pressing the NEXT key will display the following screen.
VAV Box Max Stroke Time: 0 Min
Factory Presets: 6 Min
Possible Values: 0-10
1. Pressing the NEXT key will display the following screen.