EasyManua.ls Logo

Trane IntelliPak Signature Series - Page 38

Trane IntelliPak Signature Series
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
38
Programming
PKG-SVP01B-EN
End of Submenu (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and all units with a waterside economizer)
Water Flow Control Setup Submenu
Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and all units with a waterside economizer)
Periodic Water Purge Function: ENABLED
Interval: 1 Hr Duration: 1 Min
Possible Values: Enabled, Disabled
Interval = 1-999 Hrs
Duration = 1-9 Min
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and all units with a waterside economizer)
Water-Flow Init Time Delay: 1 Min
Time To Establish Water Flow Before Diag
Possible Values: 0-20 Min
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and all units with a waterside economizer)
Temp Stablization Time Delay: 1 Min
Water Flow Time For Valid Temp Readings
Possible Values: 0-20 Min
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units)
Head Pressure Control Inactive Min: 1 0 %
Head Pressure Control Active Min: 30 %
Possible Values: 0-100%
1. Pressing the NEXT key will display the following screen.
SETUP

Other manuals for Trane IntelliPak Signature Series