38
Programming
PKG-SVP01B-EN
End of Submenu (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and all units with a waterside economizer)
Water Flow Control Setup Submenu
Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and all units with a waterside economizer)
Periodic Water Purge Function: ENABLED
Interval: 1 Hr Duration: 1 Min
Possible Values: Enabled, Disabled
Interval = 1-999 Hrs
Duration = 1-9 Min
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and all units with a waterside economizer)
Water-Flow Init Time Delay: 1 Min
Time To Establish Water Flow Before Diag
Possible Values: 0-20 Min
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and all units with a waterside economizer)
Temp Stablization Time Delay: 1 Min
Water Flow Time For Valid Temp Readings
Possible Values: 0-20 Min
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units)
Head Pressure Control Inactive Min: 1 0 %
Head Pressure Control Active Min: 30 %
Possible Values: 0-100%
1. Pressing the NEXT key will display the following screen.
SETUP