40
Programming
PKG-SVP01B-EN
(On all air-cooled units)
Cond Temp Control Band
Temporary Low Limit Suppression: 10 F
Factory Presets: 10 F
Possible Values: 0-20 F
1. Pressing the NEXT key will display the following screen.
(On all air-cooled units)
Cond Temp
Efficiency Check Point: 105 F
Factory Presets: 105 F
Possible Values: 95-115 F
1. Pressing the NEXT key will display the following screen.
(On all air-cooled units)
Cond Temp
Low Ambient Control Point: 90 F
Factory Presets: 90 F
Possible Values: 80-100 F
1. Pressing the NEXT key will display the following screen.
End of Submenu (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
Sensor Source Selections Submenu
Sensor Source Selections Submenu
Press ENTER to Review or Adjust
1.
Pressing the NEXT key will display the following screen.
(On units with electric, hydronic, or external heat and supply air temperature
control)
For Daytime Warmup Temp Ctrl, Use Sensor
Connected To: RTM ZONE TEMP INPUT
Possible Values: RTM Zone Temp Input
NSB Zone Sensor
RTM Aux Temp Input
Heat Module Aux Temp Input
ECEM Return Air Temp Input
1. Pressing the NEXT key will display the following screen.