Programming
SETUP
(On air-cooled units with low ambient damper)
Actuator Setup Num 1 Low Ambient
Direct/Reverse Act DIRECT ACTING
Factory Presets: Direct Acting
Possible Values: Direct Acting, Reverse Acting
1. Pressing the NEXT key will display the following screen.
(On air-cooled units with low ambient damper)
Actuator Setup Num 2 Low Ambient
Max Stroke Time 60 Sec
Factory Presets: 60 Sec
Possible Values: 1-255 Sec
1. Pressing the NEXT key will display the following screen.
(On air-cooled units with low ambient damper)
Actuator Setup Num 2 Low Ambient
Min Voltage 2.0 VDC
Factory Presets: 2.0 VDC
Possible Values: 0.0-9.9 VDC
1. Pressing the NEXT key will display the following screen.
(On air-cooled units with low ambient damper)
Actuator Setup Num 2 Low Ambient
Max Voltage 10.0 VDC
Factory Presets: 10.0 VDC
Possible Values: 0.1-10.0 VDC
1. Pressing the NEXT key will display the following screen.
(On air-cooled units with low ambient damper)
Actuator Setup Num 2 Low Ambient
Direct/Reverse Act DIRECT ACTING
Factory Presets: Direct Acting
Possible Values: Direct Acting, Reverse Acting
1. Pressing the NEXT key will display the following screen.
End of Submenu (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.