70
Programming
PKG-SVP01B-EN
(On units with electric heat)
Heat Stages
Stage Off
Factory Presets: 0%
Possible Values: 0-100%, Auto
Note: Only single stage electric heat is available factory installed.
1. Press the NEXT key again to display the following screen.
(On units with an airside economizer)
OA Damper Pos 0 %
Factory Presets: OA Damper = 0%
Possible Values: OA Damper = 0-100%
1. Press the NEXT key again to display the following screen.
(On units with VFD and bypass)
Supply Fan Bypass Relay: NORMAL
Possible Values: Normal, Bypass
1. Press the NEXT key again to display the following screen.
(On units with VOM)
Ventilation Override Module Output Relay
OFF
Factory Presets: Off
Possible Values: On, Off
1. Press the NEXT key again to display the following screen.
(On units with VCM)
OA Preheater State OFF
Factory Presets: Off
Possible Values: On, Off
1. Press the NEXT key to advance the cursor to the next field within this screen.
2. Press the NEXT key again to display the following screen.
SERVICE MODE