RT-SVP011A-EN 65
Troubleshooting
Supply Fan 1
Proving Failure
Supply Fan 1
Proving Failure
Supply Fan 1
Proving
Unit Warning with
Special Action
Latching All Any time the Supply Fan is expected to be running in Non
Bypass Mode, this diagnostic will be generated when a No
Flow condition exists for 40 continuous seconds.
Failure with Supply Fan 2 available:
Generate Supply Fan 1 Proving Failure
Diagnostic and Lockout all heating operation.
Failure with Supply Fan 2 NOT available:
Generate Supply Fan 1 Proving Failure
Shutdown the unit
Remote
Supply Fan 2
Proving Failure
Supply Fan 2
Proving Failure
Supply Fan 2
Proving
Unit Warning with
Special Action
Latching All Any time the Supply Fan 2 is expected to be running in
Non Bypass Mode, this diagnostic will be generated when
a No Flow condition exists for 40 continuous seconds.
Failure with Supply Fan 2 available:
Generate Supply Fan 1 Proving Failure
Diagnostic and Lockout all heating operation.
Failure with Supply Fan 2 NOT available:
Generate Supply Fan 1 Proving Failure
Shutdown the unit
Remote
Relief Fan x
Proving Failure
Relief Fan x
Proving Failure
Relief Fan x
Proving
Unit Warning with
Special Action
Non-Latching All Relief Fan x is expected to be running, this diagnostic will
be generated when a No Flow condition exists for 40
continuous seconds.
Failure w/ other relief fans available:
Generate RF x diagnostic. Take no other action.
Failure w/ no other relief fans available:
The relief damper will be closed, the relief fan will be
commanded off, economizing will be disabled and the
outside air damper will be driven to the active minimum
position.
Remote
Space Pressure
Low
Space Pressure
Low
Space Pressure
Low
Unit Warning
with Special
Action
Non-Latching All The space pressure was low
Incomplete: Will re-visit when doing Return Fan
Remote
Space Pressure
Low
Space Pressure
Low
Space Pressure
Low
Unit Warning
with Special
Action
Non-Latching All The space pressure was low
Incomplete: Will re-visit when doing Return Fan
Remote
Suction
Temperature 1
Cktx
Suction
Temperature 1
Cktx
Suction Temp
Sensor
Circuit Immediate
Shutdown
Latching All The suction temperature sensor has failed out of range. Remote
Diagnostic Name
and Source
Affects
Target
Severity Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level