RT-SVP011A-EN 83
Troubleshooting
TD7 Automatic Rediscover and Automatic Hardware Reboot
When performing one or more of the following actions listed below, a message will appear on the
screen that the TD7 is updating data (Figure 58, p. 84).
Comm Loss:
Power Meter
Comm Loss:
Power Meter
Comm: Power
Meter
Unit Warning Non-Latching All Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss:
Space
Temperature
Unit Warning Non-Latching All Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss:
Changeover
Wired
Unit Warning Non-Latching All Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Duct
Static Pressure
Local
Unit Warning Non-Latching All Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss:
Space Temp
Cooling Stpt
Wired
Unit Warning Non-Latching All Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss:
Space Temp
Heating Stpt
Wired
Unit Warning Non-Latching All Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss:
System Mode
Wired
Unit Warning Non-Latching All Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss:
System Mode
Wired
Unit Warning Non-Latching All Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Final
Filter Pressure
Sensor
Comm Loss: Final
Filter Pressure
Sensor
Invalid Final Filter
Press
Unit Warning Non-Latching All Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Pre
Filter Pressure
Sensor
Comm Loss: Pre
Filter Pressure
Sensor
Invalid Pre Filter
Pressure
Unit Warning Non-Latching All Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Diagnostic Name
and Source
Affects
Target
Severity Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level

Table of Contents

Other manuals for Trane IntelliPak

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane IntelliPak and is the answer not in the manual?

Trane IntelliPak Specifications

General IconGeneral
BrandTrane
ModelIntelliPak
CategoryAir Conditioner
LanguageEnglish

Related product manuals