February 2021
ARTC-SVX002A-EN
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of
heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training.
Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are
attached to the equipment.
Manhattan™ Gen II Water-Cooled
Modular Chiller
Installation, Operation, and Maintenance

Table of Contents

Questions and Answers

  • E
    Edward DavisSep 3, 2025
    What happens if UI3 sensor fails in Trane Manhattan Gen II Chiller?
    • S
      sydney72Sep 4, 2025
      Circuit 1 will be shut down.
  • S
    shelbybrownSep 18, 2025
    What happens if System Hot LWT is too low in Trane Chiller?
    • C
      Chelsea CruzSep 18, 2025
      A warning will be displayed.
  • A
    Ashley GreenSep 16, 2025
    What happens if UI11 sensor fails in Trane Manhattan Gen II?
    • Z
      zbrownSep 16, 2025
      Control panel heating / cooling control is disabled.
  • J
    Joshua JimenezSep 14, 2025
    What happens if LP Alarm is triggered in Trane Manhattan Gen II Chiller?
    • J
      Joseph DennisSep 14, 2025
      Circuit 1/2 will be shut down.
  • S
    Scott SantiagoSep 12, 2025
    What happens if HP Alarm is triggered in Trane Chiller?
    • W
      wilsonheatherSep 12, 2025
      Circuit 1/2 will be shut down.
  • M
    melissaweissSep 12, 2025
    What happens if System Chilled LWT is too high in Trane Manhattan Gen II Chiller?
    • T
      Terry SmithSep 12, 2025
      A warning will be displayed.
  • T
    Tammy FreemanSep 9, 2025
    What to do if UI6 sensor fails in Trane Manhattan Gen II?
    • S
      Stephen WebbSep 9, 2025
      If the Module is in Stand-alone Mode and respective Entering / Leaving Water sensor selected for Temperature, Free Cooling control will be shut down.
  • E
    Eric DavisSep 7, 2025
    What to do if UI5 sensor fails in Trane Manhattan Gen II Chiller?
    • V
      Veronica ShieldsSep 7, 2025
      If the Module is in Stand-alone Mode and respective Entering / Leaving Water sensor selected for Temperature, local heating control will be shut down.
  • K
    Kimberly EstradaSep 5, 2025
    What to do if UI3 sensor fails in Trane Manhattan Gen II?
    • N
      nsilvaSep 5, 2025
      If the Module is in Stand-alone Mode and respective Entering / Leaving Water sensor selected for Temperature, local cooling control will be shut down.
  • K
    Katie MooreAug 20, 2025
    What happens if client communication is lost in a Trane Manhattan Gen II?
    • J
      Jamie GonzalezAug 20, 2025
      If the client communication is lost, Trane Chiller server modules will switch into Stand-alone Mode.

Trane Manhattan Gen II Specifications

General IconGeneral
Tonnage150 - 500 tons
RefrigerantR-134a
Full Load Efficiency0.62 kW/ton
Sound Level85 dBA
Operating Voltage460V/3/60Hz
Operating Temperature Range (Leaving Chilled Water)40°F