What happens if there is a Condenser Flow Alarm in Trane Manhattan Gen II Chiller?
- EElizabeth MoraSep 2, 2025
Circuits or Circuit 1 in Constant Flow systems will be shut down.

What happens if there is a Condenser Flow Alarm in Trane Manhattan Gen II Chiller?
Circuits or Circuit 1 in Constant Flow systems will be shut down.
What happens if there is an Evaporator Freezing Alarm in Trane Manhattan Gen II?
The module will be locked out.
What happens if there is an Evaporator Flow Alarm in Trane Manhattan Gen II?
The module will be locked out in Variable Flow systems.
What happens if Phase Monitor Alarm is triggered in Trane Chiller?
The module will be locked out.
What happens when UI1 sensor fails in Trane Manhattan Gen II Chiller?
If the UI1 sensor fails and it is selected for Suction Pressure Alarm, circuit 1 will be shut down.
What to do if UI4 sensor fails in Trane Manhattan Gen II?
If the UI4 sensor fails, the module will be locked out.
What to do if UI2 sensor fails in Trane Chiller?
If the UI2 sensor fails, Circuit 1 will be shut down.
| Tonnage | 150 - 500 tons |
|---|---|
| Refrigerant | R-134a |
| Full Load Efficiency | 0.62 kW/ton |
| Sound Level | 85 dBA |
| Operating Voltage | 460V/3/60Hz |
| Operating Temperature Range (Leaving Chilled Water) | 40°F |