Installation - Electrical
RTAC-SVX01J-EN 97
BACnet Protocol
Data Link Layer Options
Multistate
Value
Object_Identifier
Object_Name
Object_Type
Present_Value
Status_Flags
Event_State
Out_Of_Service
Number_Of_States
Object_Name
Description
State_Text
Out_Of_Service
Present_Value
Reliability
Priority_Array
Relinquish_Default
Time_Delay
Notification_Class
Alarm_Values
Fault_Values
Event_Enable
•Notify_Type
State_Text
Reliability
Relinquish_Default
Time_Delay
Notification_Class
Alarm_Values
Fault_Values
Event_Enable
Acked_Transitions
•Notify_Type
Event_Time_Stamps
Yes
Yes, only
user
created
objects
Notification
Class
Object_Identifier
Object_Name
Object_Type
Notification_Class
•Priority
Ack_Required
Recipient_List
Object_Name
•Priority
Ack_Required
Recipient_List None Yes
Yes, only
user
created
objects
Trend
Object_Identifier
Object_Name
Object_Type
Log_Enable
Stop_When_Full
Buffer_Size
Log_Buffer
Record_Count
Total_Record_Count
Event_State
Object_Name
Log_Enable
Start_Time
Stop_Time
Log_DeviceObjectPropert
y
Log_Interval
Stop_When_Full
Buffer_Size
Log_Buffer
Record_Count
Notification_Threshold
Notification_Class
Event_Enable
•Notify_Type
Start_Time
Stop_Time
Log_DeviceObjectProperty
Log_Interval
Stop_When_Full
Buffer_Size
Notification_Threshold
Records_Since_Notification
Last_Notify_Record
Notification_Class
Event_Enable
Acked_Transitions
Event_Time_Stamps
Yes
Yes, only
user
created
objects
(a)Properties written for Present_Value and Reliability only if Out_of_Service is TRUE.
Table 46. Descriptions and configurations (continued)
Object
Type
Required Properties Read Properties Written
(a)
Optional Properties Read
Ability
to
Create
Ability to
Delete
Data Link Layer Description
Supported
Option
ANSI/ATA 878.1, 2.5 Mb ARCNET (Clause 8)
ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), Baud
Rate(s)
BACnet IP, (Annex J)
BACnet IP, (Annex J), Foreign Device
ISO 8802-3, Ethernet (Clause 7)(10Base2, 10Base5,
10BaseT, Fiber)
LonTalk, (Clause 11), Medium
MS/TP Master (Clause 9), Baud Rate(s): 9600,
19200, 38400, 76800, and 115200 @1.5% Nominal
Baud Rate
ü
MS/TP Slave (Clause 9), Baud Rate(s)
Other
Point-to-Point, EIA 232 (Clause 10), Baud Rate(s):
9600, 19200, 38400
Point-to-Point, Modem (Clause 10), Baud Rate(s):
9600, 19200, 38400

Table of Contents

Other manuals for Trane R Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane R Series and is the answer not in the manual?

Trane R Series Specifications

General IconGeneral
BrandTrane
ModelR Series
CategoryChiller
LanguageEnglish

Related product manuals