Unit Startup
148 RT-SVX24J-EN
Table 44. Standard units with ERW field measured plenum pressure
Low CFM ERW — 90-162 Tons
90/100 Ton Low CFM ERW - Field measured plenum pressure (inches wc)
OA Actuator Reading [Degrees] RA Actuator Reading [Degrees]
60 50 40 30 20 10 0 10 20 30 35 40 45 50
CFM
Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ E/T E/T E/T E/T E/T E/T E/T E/T
16000 1.29 0.87 1.52 0.71 1.05 0.64 0.84 0.60 0.64 0.58 0.63 0.46 0.45 0.43 0.41 0.38 0.35 0.32 0.20
20000 1.99 1.34 2.34 1.09 1.62 0.98 1.28 0.92 0.97 0.89 0.96 0.69 0.68 0.65 0.62 0.57 0.52 0.48 0.29
25000 2.07 1.68 2.49 1.50 1.97 1.41 1.49 1.36 1.47 1.04 1.02 0.99 0.93 0.86 0.78 0.71 0.42
30000 2.94 2.39 2.13 2.79 1.99 2.09 1.93 2.08 1.46 1.43 1.37 1.30 1.19 1.08 0.98 0.56
33000 ————2.86 2.54 2.38 2.50 2.30 2.48 1.73 1.70 1.63 1.54 1.41 1.28 1.15 0.65
36000 ——————3.00 2.80 2.94 2.71 2.92 2.02 1.98 1.91 1.79 1.64 1.48 1.34 0.74
40000 ————————————2.46 2.41 2.32 2.18 1.98 1.79 1.61 0.87
105/118 Ton Low CFM ERW - Field measured plenum pressure (inches wc)
OA Actuator Reading [Degrees] RA Actuator Reading [Degrees]
60 50 40 30 20 10 0 10 20 30 35 40 45 50
CFM
Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ E/T E/T E/T E/T E/T E/T E/T E/T
19000 1.80 1.22 2.12 0.99 1.46 0.89 1.16 0.83 0.88 0.81 0.88 0.63 0.62 0.59 0.56 0.52 0.48 0.44 0.27
23000 2.63 1.76 1.44 2.12 1.29 1.68 1.21 1.27 1.17 1.26 0.90 0.88 0.85 0.80 0.74 0.68 0.62 0.37
28000 2.57 2.09 1.86 2.45 1.74 1.84 1.69 1.82 1.28 1.25 1.21 1.14 1.05 0.95 0.86 0.50
33000 ————2.86 2.54 2.38 2.50 2.30 2.48 1.73 1.70 1.63 1.54 1.41 1.28 1.15 0.65
38000 ————————————2.24 2.20 2.11 1.98 1.81 1.64 1.48 0.81
43000 ————————————2.80 2.74 2.64 2.47 2.25 2.03 1.83 0.97
45000 ————————————3.04 2.98 2.86 2.68 2.44 2.20 1.97 1.04
120/128 Ton Low CFM ERW - Field measured plenum pressure (inches wc)
OA Actuator Reading [Degrees] RA Actuator Reading [Degrees]
60 50 40 30 20 10 0 10 20 30 35 40 45 50
CFM
Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ E/T E/T E/T E/T E/T E/T E/T E/T
21000 1.54 1.08 1.69 0.90 1.08 0.82 0.89 0.78 0.87 0.76 0.75 0.58 0.56 0.54 0.50 0.44 0.39 0.34 0.14
26000 2.33 1.62 2.56 1.35 1.62 1.23 1.33 1.16 1.30 1.13 1.11 0.84 0.82 0.78 0.72 0.64 0.56 0.49
31000 2.26 1.88 2.25 1.70 1.85 1.61 1.80 1.56 1.53 1.15 1.12 1.07 0.98 0.87 0.75 0.65
36000 2.99 2.48 2.98 2.24 2.44 2.11 2.37 2.05 2.00 1.50 1.46 1.38 1.27 1.11 0.96 0.81
41000 ——————2.85 2.68 2.60 2.54 1.89 1.84 1.74 1.59 1.39 1.19 1.00
46000 ————————————2.31 2.24 2.12 1.93 1.68 1.42 1.19
51000 ————————————2.77 2.69 2.54 2.31 2.00 1.69 1.40
54000 ————————————3.16 3.06 2.89 2.64 2.29 1.94 1.61
continued on next page