120/128 Ton Standard CFM ERW - Field measured plenum pressure (inches wc)
OA Actuator Reading [Degrees] RA Actuator Reading [Degrees]
60 50 40 30 20 10 0 10 20 30 35 40 45
CFM
Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ E/T E/T E/T E/T E/T E/T E/T
21000 1.48 1.02 1.63 0.84 1.02 0.76 0.83 0.72 0.81 0.70 0.68 0.51 0.50 0.47 0.44 0.38 0.33 0.28
26000 2.23 1.53 2.47 1.26 1.52 1.13 1.24 1.07 1.21 1.04 1.01 0.75 0.73 0.69 0.63 0.55 0.47 0.40
31000 2.13 1.75 2.12 1.57 1.72 1.48 1.67 1.43 1.40 1.02 0.99 0.94 0.85 0.74 0.62 0.52
36000 2.83 2.31 2.81 2.07 2.27 1.95 2.20 1.89 1.84 1.34 1.29 1.22 1.11 0.95 0.79 0.65
41000 2.95 2.63 2.89 2.47 2.80 2.39 2.33 1.68 1.62 1.53 1.38 1.18 0.98
46000 2.96 2.88 2.06 1.99 1.87 1.68 1.43 1.17
51000 2.47 2.39 2.24 2.01 1.70 1.39
54000 2.74 2.65 2.48 2.22 1.87 1.52
130-162 Ton Standard CFM ERW - Field measured plenum pressure (inches wc)
OA Actuator Reading [Degrees] RA Actuator Reading [Degrees]
60 50 40 30 20 10 0 10 20 30 35 40 45
CFM
Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ E/T E/T E/T E/T E/T E/T E/T
23000 1.73 1.18 1.92 0.97 1.18 0.87 0.96 0.82 0.93 0.80 0.78 0.58 0.56 0.53 0.48 0.42 0.35 0.30
26000 2.19 1.49 2.43 1.22 1.48 1.09 1.20 1.03 1.16 1.00 0.97 0.71 0.69 0.65 0.59 0.51 0.43 0.35
30000 2.89 1.95 1.59 1.94 1.42 1.56 1.34 1.52 1.29 1.26 0.91 0.88 0.83 0.75 0.64 0.54 0.44
35000 2.59 2.11 2.58 1.88 2.07 1.76 2.01 1.71 1.66 1.19 1.15 1.08 0.97 0.82 0.67
40000 2.71 2.41 2.66 2.26 2.57 2.18 2.12 1.50 1.45 1.36 1.22 1.02 0.83
45000 3.00 2.80 2.71 2.63 1.84 1.78 1.66 1.49 1.24 1.00
50000 2.23 2.15 2.01 1.79 1.49 1.19
55000 2.65 2.55 2.38 2.11 1.75
58000 2.91 2.80 2.61 2.31 1.91