EasyManua.ls Logo

Trane Sintesis Advantage CGAF 100 SE - Page 76

Trane Sintesis Advantage CGAF 100 SE
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
76
CG-SVX039C-GB
Refrigerant and Oil-charge
Management
Proper oil and refrigerant charge is essential for proper
unit operation, unit performances, and environmental
protection. Only trained and licensed service personnel
should service the chiller.
Some of the symptoms of a refrigerant under-charged
unit:
Larger-than-normal evaporator approach temperatures
(leaving water temperature – saturated evaporator
temperature). If the refrigerant charge is correct the
approach temperature is 4°C. These values are given
for units running at full load and with water without
antifreeze
Low Evaporator-refrigerant temperature limit
Low Refrigerant-Temperature cutout diagnostic
Fully-open expansion valve
Possible whistling sound coming from liquid line
(due to high vapour velocity)
High condenser + Sub cooler pressure drop
Some of the symptoms of a refrigerant over-charged unit
Condenser Pressure Limit
High –Pressure Cutout diagnostic
More-than-normal number of fans running
Erratic fan control
Higher-than-normal compressor power
Some of the symptoms of an oil over-charged unit
Larger-than-normal evaporator approach temperatures
(Leaving-water-temperature – Saturated Evaporator
Temperature)
Low Evaporator-refrigerant Temperature limit
Low Refrigerant – Temperature Cutout diagnostic
Low unit capacity
High oil-sump level after normal shutdown
Discharge temperature is lower than prediction
provided by compressor manufacturer selection
program.
Some of the symptoms of an oil under-charged unit
Seized or Welded compressors
Low oil-sump level after normal shutdown
Periodic Maintenance

Related product manuals