11UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
Evaporator Glycol Requirement
Table 25 – Leaving water temperature cutout & glycol mass percent recommended for RTAF chillers with
Standard tubes
Ethylene Glycol
Unit type
∆T evaporator
coolant (K)
2 3 4 5 6 7 8
LWT (°C) LWTC (°C) %wt Glycol %wt Glycol %wt Glycol %wt Glycol %wt Glycol %wt Glycol %wt Glycol
4 1.2 - 4 4 4 4 4 5
2 -0.8 - 8 8 9 10 12 -
0 -2.8 13 13 13 15 19 - -
-2 -4.8 18 18 19 - - - -
-4 -6.8 22 22 - - - - -
-5 -7.8 24 25 - - - - -
-6 -8.8 25 29 - - - - -
-7 -9.8 27 - - - - - -
-8 -10.8 29 - - - - - -
-9 -11.8 31 - - - - - -
-10 -12.8 - - - - - - -
-11 -13.8 - - - - - - -
-12 -14.8 - - - - - - -
Table 26 – Leaving water temperature cutout & glycol mass percent recommended for RTAF chillers with
Standard tubes
Monopropylene Glycol
Unit type
∆T evaporator
coolant (K)
2 3 4 5 6 7 8
LWT (°C) LWTC (°C) %wt Glycol %wt Glycol %wt Glycol %wt Glycol %wt Glycol %wt Glycol %wt Glycol
4 1.2 - 4 4 4 4 5 -
2 -0.8 10 9 10 12 - - -
0 -2.8 15 16 21 - - - -
-2 -4.8 20 - - - - - -
-4 -6.8 27 - - - - - -
-5 -7.8 - - - - - - -
-6 -8.8 - - - - - - -
-7 -9.8 - - - - - - -
-8 -10.8 - - - - - - -
The table above is for RTAF sizes 090 to 245. For RTAF sizes 250 to 550, please consult your local Trane Sales Office.