ACC-APG002A-EN
31
Table 6. 0 to 100% economizer variable speed supply fan (continued)
Supply Fan
Compensa-
tion
Demand
Controlled
Ventilation
Remote
Minimum
Position
Occupancy
Status
Outdoor Air Damper Controlling Setpoints
DCV Minimum OA Damper Position at Mid Fan Capacity
DCV Minimum OA Damper Position at Min Fan Capacity
Enabled
Not Installed
or Disabled
Installed
Occupied,
Occupied
Bypass
Remote Minimum Position (Full Fan Capacity)
Design Minimum OA Damper Position at Mid Fan Capacity
Design Minimum OA Damper Position at Min Fan Capacity
Enabled
Not Installed
or Disabled
Not Installed
Occupied,
Occupied
Bypass
Design Minimum OA Damper Position at Full Fan Capacity
Design Minimum OA Damper Position at Mid Fan Capacity
Design Minimum OA Damper Position at Min Fan Capacity
Enabled Installed
Installed or
Not Installed
Occupied
Standby
Design Minimum OA Damper Position at Full Fan Capacity
Design Minimum OA Damper Position at Mid Fan Capacity
Design Minimum OA Damper Position at Min Fan Capacity
Standby Minimum OA Damper Position at Full Fan Capacity
Standby Minimum OA Damper Position at Mid Fan Capacity
Standby Minimum OA Damper Position at Min Fan Capacity
Disabled
Installed or
Not Installed
Installed or
Not Installed
Any Economizer Minimum Position Setpoint
Table 7. 0 to 100% economizer multi-speed supply fan (2–speed)
Supply Fan
Compensa-
tion
Demand
Controlled
Ventilation
Remote
Minimum
Position
Occupancy
Status
Outdoor Air Damper Controlling Setpoints
Enabled Installed Installed
Occupied,
Occupied
Bypass
Supply Fan at 100%:
Remote Minimum Position
DCV Minimum OA Damper Position at Full Fan Capacity
Supply Fan at minimum speed:
Design Minimum OA Damper Position at Min Fan Capacity
DCV Minimum OA Damper Position at Min Fan Capacity
Enabled Installed Not Installed
Occupied,
Occupied
Bypass
Supply Fan at 100%:
Design Minimum OA Damper Position at Full Fan Capacity
DCV Minimum OA Damper Position at Full Fan Capacity
Supply Fan at minimum speed:
Design Minimum OA Damper Position at Min Fan Capacity
DCV Minimum OA Damper Position at Min Fan Capacity
Enabled
Not Installed
or Disabled
Installed
Occupied,
Occupied
Bypass
Supply Fan at 100%:
Remote Minimum Position
Supply Fan at minimum speed:
Design Minimum OA Damper Position at Min Fan Capacity
Outdoor Air Damper Control