ACC-APG002A-EN
57
Heating setpoint low limit
Cooling setpoint high limit
Cooling setpoint low limit
These setpoint limits apply only to the occupied and occupied standby, heating, and cooling setpoints.
They do not apply to the unoccupied heating and cooling setpoints. When the controller is in the
unoccupied mode, it always uses the unoccupied heating and cooling setpoints.
Dual Setpoint
When Symbio™ 700 is configured for system types CVZT or VVZT, the controls can be configured for
Dual Setpoint control. Dual Setpoint provides independent space cooling setpoint and space heating
setpoint inputs to the controller. It also allows an external source to write to independent the space
cooling and heating setpoints.
Appendix A