34
ACC-APG002A-EN
Refer to the Diagnostics section for specific diagnostics generated based on the Compressor Proving
signals.
Compressor Low Pressure Cutout Control
For each compressor/circuit, a normally CLOSED low pressure cutout input is monitored for equipment
protection on the Symbio™ 700. When a low pressure event is active, the input becomes OPEN and
diagnostics are generated as described below. Refer to the Diagnostics section below for specific
diagnostics that are generated based on the circuit Low Pressure Cutout inputs.