Menu Definitions
20 BAS-SVN028K-EN
Erase all?
Resets the sensor back to factory settings.
Are you sure?
Confirms the erase reset.
UC17 config
Defines the sensor connected to electrical terminals 17 and 18.
None – terminal not in use.
Motion – motion sensor or external dry contact.
Temp – 10K temperature sensor.
Temp. sensor
Defines the location of the space temperature sensor used for control.
Internal – sensor internal to the zone sensor.
Remote – sensor wired to the HVAC equipment.
Wired – sensor wired to zone sensor terminals 17 and 18.
Occupancy src
Defines the source of the occupancy signal.
Schedule – zone sensor time schedule.
Motion – motion sensor or external dry contact wired to zone sensor.
(a)The parameter is only displayed when the zone sensor is connected to a ReliaTel or Symbio 800 control system.