Menu Definitions
24 BAS-SVN028K-EN
Service View
1/7 Service View
Firmware rev – current firmware installed on sensor.
Room temp. – current air temperature in the space.
Occupancy state – occupancy state being sent to HVAC equipment unit status.
Temp. source – location of the space temperature sensor currently in use:
Internal: Sensor internal to zone sensor.
Wired: External sensor wired to zone sensor terminals 17 and 18.
Remote: External sensor wired to HVAC equipment controller.
2/7 Service View
ReliaTel/Symbio 800
OA temp. – outdoor air temperature.
DA temp. – discharge air temperature.
RA temp. – return air temperature.
MA temp. – mixed air temperature.
RH – indoor relative humidity.
OA RH – outdoor relative humidity.
Note: Discharge air sensor is an optional sensor for Symbio 800 controlled equipment.
2/7 Service View UC400
DA temp. – discharge air temperature.
RH - indoor relative humidity.
3/7 Service View
ReliaTel/Symbio 800
Econ. available: Yes – OA conditions allow economizing.
Economizer: On – HVAC equipment currently economizing.
Cooling: On – HVAC equipment is cooling.
Primary heat: On – HVAC equipment is heating.
Secondary heat: On – Secondary heat source is heating.
Note: The Symbio 800 does not support a secondary heat source.
3/7 Service View UC400
Cooling – HVAC equipment is cooling.
Primary heat – HVAC equipment is heating.
Secondary heat – Secondary heat source is heating.
4/7 Service View ReliaTel/
Symbio 800
Unit status: Indicates if BACnet data is being passed between the HVAC equipment and
the zone sensor.
Online: data is being passed.
Offline: data is not being passed.
MAT low limit: On – economizer is being limited due to low mixed
air temperature. Off – normal temp.
DAT sensor fail: On – sensor fail. Off – sensor normal.
OAT sensor fail: On – sensor fail. Off – sensor normal.
RAT sensor fail: On – sensor fail. Off – sensor normal.
MAT sensor fail: On – sensor fail. Off – sensor normal.
Note: Symbio 800 does not use the mixed air sensor for economizer control.
4/7 Service View UC400
Indicates if BACnet data is being passed between the HVAC equipment and the zone
sensor.
Online: data is being passed.
Offline: data is not being passed.
5/7 Service View ReliaTel/
Symbio 800
Econo fail close: On – OA damper is open when it should not be.
Off – normal.
Econo fail open: On – OA damper is not open when it should be.
Off – normal.
Blocked OA: On – No outdoor air to equipment. Off – normal.
Excessive OA: On – excessive outdoor air. Off – normal.
5/7 Service View UC400 No items to display.
6/7 Service View
Shed input: displays status of dry contact between terminals 16 and 18.
Shed demand: displays status of BACnet load shed command. Can be modified for testing
purposes. This is the only field that is configurable in Service View.
7/7 Service View
Device Name: VTR810xAxxxx-2.
Graphic Library Revision: 3.0.1.