Table 15. BMS BO Objects: Status, alarms, and faults (continued)
Tag Name Array
Object
Type
Instance
Metasys N2
Address
Modbus
Register
EIP Read Tag
Name
EIP Write Tag Name
Chiller: Evaporator Flow Fault
ChillerFaults BO 253 145 10201
ChillerFaults[0] WR_ChillerFaults[0]
Chiller: Condenser Flow Fault ChillerFaults BO 254 146 10202
ChillerFaults[1] WR_ChillerFaults[1]
Chiller: Communication Fault ChillerFaults BO 255 147 10203
ChillerFaults[2] WR_ChillerFaults[2]
Chiller: Evaporator Flow Fault with DPS
ChillerFaults BO 256 148 10204
ChillerFaults[3] WR_ChillerFaults[3]
Chiller: Condenser Flow Fault with DPS ChillerFaults BO 257 149 10205
ChillerFaults[4] WR_ChillerFaults[4]
Chiller: Fan Fault FB1 ChillerFaults BO 258 150 10206
ChillerFaults[5] WR_ChillerFaults[5]
Chiller: Fan Fault FB2 ChillerFaults BO 259 151 10207
ChillerFaults[6] WR_ChillerFaults[6]
Chiller: Fan Fault FB3 ChillerFaults BO 260 152 10208
ChillerFaults[7] WR_ChillerFaults[7]
Chiller: Fan Fault FB4 ChillerFaults BO 261 153 10209
ChillerFaults[8] WR_ChillerFaults[8]
Chiller: HeatTrace Fault ChillerFaults BO 262 154 10210
ChillerFaults[9] WR_ChillerFaults[9]
Chiller: Adiabatic System Fault
ChillerFaults BO 263 155 10211
ChillerFaults[10] WR_ChillerFaults[10]
Chiller: Spare Fault 1
ChillerFaults BO 264 156 10212
ChillerFaults[11] WR_ChillerFaults[11]
Chiller: Spare Fault 2
ChillerFaults BO 265 157 10213
ChillerFaults[12] WR_ChillerFaults[12]
Chiller: Spare Fault 3
ChillerFaults BO 266 158 10214
ChillerFaults[13] WR_ChillerFaults[13]
Chiller: Spare Fault 4
ChillerFaults BO 267 159 10215
ChillerFaults[14] WR_ChillerFaults[14]
Chiller: Spare Fault 5
ChillerFaults BO 268 160 10216
ChillerFaults[15] WR_ChillerFaults[15]
Chiller: Evaporator Pump1 Fault
ChillerFaults BO 269 161 10217
ChillerFaults[16] WR_ChillerFaults[16]
Chiller: Evaporator Pump1 Flow Alarm
ChillerFaults BO 270 162 10218
ChillerFaults[17] WR_ChillerFaults[17]
Chiller: Evaporator Pump2 Fault
ChillerFaults BO 271 163 10219
ChillerFaults[18] WR_ChillerFaults[18]
Chiller: Evaporator Pump2 Flow Alarm
ChillerFaults BO 272 164 10220
ChillerFaults[19] WR_ChillerFaults[19]
Chiller: No Chiller Pump Available
ChillerFaults BO 273 165 10221
ChillerFaults[20] WR_ChillerFaults[20]
Chiller: Condenser Pump1 Fault
ChillerFaults BO 274 166 10222
ChillerFaults[21] WR_ChillerFaults[21]
Chiller: Condenser Pump1 Flow Alarm
ChillerFaults BO 275 167 10223
ChillerFaults[22] WR_ChillerFaults[22]
Chiller: Condenser Pump2 Fault
ChillerFaults BO 276 168 10224
ChillerFaults[23] WR_ChillerFaults[23]
Chiller: Condenser Pump2 Flow Alarm
ChillerFaults BO 277 169 10225
ChillerFaults[24] WR_ChillerFaults[24]
Chiller: No Condenser Pump Available
ChillerFaults BO 278 170 10226
ChillerFaults[25] WR_ChillerFaults[25]
Chiller: Chiller Not Available ChillerFaults BO 279 171 10227
ChillerFaults[26] WR_ChillerFaults[26]
Chiller: No Compressor Available Fault
ChillerFaults BO 280 172 10228
ChillerFaults[27] WR_ChillerFaults[27]
Chiller: Spare Fault 6
ChillerFaults BO 281 173 10229
ChillerFaults[28] WR_ChillerFaults[28]
Chiller: Spare Fault 7
ChillerFaults BO 282 174 10230
ChillerFaults[29] WR_ChillerFaults[29]
Chiller: Spare Fault 8
ChillerFaults BO 283 175 10231
ChillerFaults[30] WR_ChillerFaults[30]
Chiller: Spare Fault 9
ChillerFaults BO 284 176 10232
ChillerFaults[31] WR_ChillerFaults[31]
Chiller: Evaporator Flow Switch
ChillerStatus BO 285 177 10301
ChillerStatus[0] WR_ChillerStatus[0]
Chiller: Condenser Flow Switch ChillerStatus BO 286 178 10302
ChillerStatus[1] WR_ChillerStatus[1]
Chiller: Evaporator Pump Enable
ChillerStatus BO 287 179 10303
ChillerStatus[2] WR_ChillerStatus[2]
Chiller: Condenser Pump Enable
ChillerStatus BO 288 180 10304
ChillerStatus[3] WR_ChillerStatus[3]
Chiller: Low Lift Active Circuit 1 ChillerStatus BO 289 181 10305
ChillerStatus[4] WR_ChillerStatus[4]
Chiller: Low Lift Active Circuit 2 ChillerStatus BO 290 182 10306
ChillerStatus[5] WR_ChillerStatus[5]
Chiller: Low Lift Active Circuit 3 ChillerStatus BO 291 183 10307
ChillerStatus[6] WR_ChillerStatus[6]
Chiller: Low Lift Active Circuit 4 ChillerStatus BO 292 184 10308
ChillerStatus[7] WR_ChillerStatus[7]