EasyManua.ls Logo

Trane TCAA Series - Page 85

Trane TCAA Series
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ARTC-SVX013A-EN
85
Table 28. Chiller/Compressor alarms/Faults listing (continued)
Code
Description
Enable Reset Period
Start-Up Steady
Active in
Off
Alarm
Relay
Warning
Realy
Circuit
System
Compressor
a1Q
TC1 AC - Soft
Start Fault
1 -1 0 0 0 X SYSTEM –
a1F
TC1 ANC -
Inverter
Temperature
1 -1 0 0 0 X X SYSTEM –
a1G
TC1 ANC -
Discharge Temp
1 -1 0 0 0 X X SYSTEM –
a1H
TC1 ANC -
Suction Pressure
1 -1 0 0 0 X SYSTEM –
a1I
TC1 ANC -
Discharge
Pressure
1 -1 0 0 0 X SYSTEM –
a1J
TC1 ANC - 3
Phase Current Trip
1 -1 0 0 0 X X SYSTEM –
a1K
TC1 ANC - Shaft
Cavity
Temperature
1 -1 0 0 0 X X SYSTEM –
a1L
TC1 ANC -
Leaving Water
1 -1 0 0 0 X X SYSTEM –
a1M
TC1 ANC - Total
Compression
Ratio Fault
1 -1 0 0 0 X X SYSTEM –
a1N
TC1 ANC - SCR
Temperature
1 -1 0 0 0 X SYSTEM –
a1O
TC1 ANC - Super
Heat
1 -1 0 0 0 X X SYSTEM –
a1X
TC1 ANC -
EEPROM
checksum error
1 -1 0 0 0 X SYSTEM –
a1Y
TC1 AC Generator
mode
1 -1 0 0 0 X NO –
Compressor #2
aC2
TC2
communication
error
1 -1 0 60 0 X SYSTEM –
a21
TC2 AC - Inverter
Temperature
1 -1 0 0 0 X X SYSTEM –
a22
TC2 AC -
Discharge Temp
1 -1 0 0 0 X X SYSTEM –
a23
TC2 AC - Suction
Pressure
1 -1 0 0 0 X X SYSTEM –
a24
TC2 AC -
Discharge
Pressure
1 -1 0 0 0 X X SYSTEM –
a25
TC2 AC - 3 Phase
Current Trip
1 -1 0 0 0 X X SYSTEM –
a26
TC2 AC - Shaft
Cavity
Temperature
1 -1 0 0 0 X X SYSTEM –
a27
TC2 AC - Leaving
Air /Water
1 -1 0 0 0 X X SYSTEM –
a28
TC2 AC - Total
Compression
Ratio Fault
1 -1 0 0 0 X X SYSTEM –
a29
TC2 AC - Bearing
Motor Fault
1 -1 0 0 0 X X SYSTEM –
a2A
TC2 AC - Sensor
error
1 -1 0 0 0 X X SYSTEM –
a2B
TC2 AC - SCR
Fault
1 -1 0 0 0 X X SYSTEM –
a2C
TC2 AC - Lock out
Fault
1 -1 0 0 0 X X SYSTEM –
a2D
TC2 AC - Motor
Thermistor
1 -1 0 0 0 X X SYSTEM –
Chiller Troubleshooting