ARTC-SVX007A-EN
41
Table 12. BMS data listing - AV and AO (continued)
Tag Name Description
Object
Type
Array
Offset
Object
Instance
Modbus
Address
DTC2 Suction
Pressure
Suction Pressure (Integer Value with 1 implied decimal) -
Compressor #2
AO 20 20 40021
DTC3 Suction
Pressure
Suction Pressure (Integer Value with 1 implied decimal) -
Compressor #3
AO 21 21 40022
DTC4 Suction
Pressure
Suction Pressure (Integer Value with 1 implied decimal) -
Compressor #4
AO 22 22 40023
DTC5 Suction
Pressure
Suction Pressure (Integer Value with 1 implied decimal) -
Compressor #5
AO 23 23 40024
DTC6 Suction
Pressure
Suction Pressure (Integer Value with 1 implied decimal) -
Compressor #6
AO 24 24 40025
DTC1 Compressor
State
Compressor State (see Details Page for State Enumeration) -
Compressor #1
AO 35 25 40036
DTC2 Compressor
State
Compressor State (see Details Page for State Enumeration) -
Compressor #2
AO 36 26 40037
DTC3 Compressor
State
Compressor State (see Details Page for State Enumeration) -
Compressor #3
AO 37 27 40038
DTC4 Compressor
State
Compressor State (see Details Page for State Enumeration) -
Compressor #4
AO 38 28 40039
DTC5 Compressor
State
Compressor State (see Details Page for State Enumeration) -
Compressor #5
AO 39 29 40040
DTC5 Compressor
State
Compressor State (see Details Page for State Enumeration) -
Compressor #6
AO 40 30 40041
DTC1 Discharge
Pressure
Discharge Pressure (Integer Value with 1 implied decimal) -
Compressor #1
AO 43 31 40044
DTC2 Discharge
Pressure
Discharge Pressure (Integer Value with 1 implied decimal) -
Compressor #2
AO 44 32 40045
DTC3 Discharge
Pressure
Discharge Pressure (Integer Value with 1 implied decimal) -
Compressor #3
AO 45 33 40046
DTC4 Discharge
Pressure
Discharge Pressure (Integer Value with 1 implied decimal) -
Compressor #4
AO 46 34 40047
DTC5 Discharge
Pressure
Discharge Pressure (Integer Value with 1 implied decimal) -
Compressor #5
AO 47 35 40048
DTC6 Discharge
Pressure
Discharge Pressure (Integer Value with 1 implied decimal) -
Compressor #6
AO 48 36 40049
Chiller Capacity Chiller Percent Capacity (Integer Value with 1 implied decimal)
AO 51 37 40052
DTC1 3-Phase
Current
Compressor Current (Integer Value with 1 implied decimal) -
Compressor #1
AO 52 38 40053
DTC2 3-Phase
Current
Compressor Current (Integer Value with 1 implied decimal) -
Compressor #2
AO 53 39 40054
DTC3 3-Phase
Current
Compressor Current (Integer Value with 1 implied decimal) -
Compressor #3
AO 54 40 40055
DTC4 3-Phase
Current
Compressor Current (Integer Value with 1 implied decimal) -
Compressor #4
AO 55 41 40056
DTC5 3-Phase
Current
Compressor Current (Integer Value with 1 implied decimal) -
Compressor #5
AO 56 42 40057
DTC6 3-Phase
Current
Compressor Current (Integer Value with 1 implied decimal) -
Compressor #6
AO 57 43 40058
Operating Procedures