Table 12. BMS data listing - AV and AO (continued)
Tag Name Description
Object
Type
Array
Offset
Object
Instance
Modbus
Address
DTC1 Suction
Temperature
Suction Temperature (Integer Value with 1 implied decimal) -
Compressor #1
AO 60 44 40061
DTC2 Suction
Temperature
Suction Temperature (Integer Value with 1 implied decimal) -
Compressor #2
AO 61 45 40062
DTC3 Suction
Temperature
Suction Temperature (Integer Value with 1 implied decimal) -
Compressor #3
AO 62 46 40063
DTC4 Suction
Temperature
Suction Temperature (Integer Value with 1 implied decimal) -
Compressor #4
AO 63 47 40064
DTC5 Suction
Temperature
Suction Temperature (Integer Value with 1 implied decimal) -
Compressor #5
AO 64 48 40065
DTC6 Suction
Temperature
Suction Temperature (Integer Value with 1 implied decimal) -
Compressor #6
AO 65 49 40066
DTC1 Discharge
Temperature
Discharge Temperature (Integer Value with 1 implied decimal) -
Compressor #1
AO 76 50 40077
DTC2 Discharge
Temperature
Discharge Temperature (Integer Value with 1 implied decimal) -
Compressor #2
AO 77 51 40078
DTC3 Discharge
Temperature
Discharge Temperature (Integer Value with 1 implied decimal) -
Compressor #3
AO 78 52 40079
DTC4 Discharge
Temperature
Discharge Temperature (Integer Value with 1 implied decimal) -
Compressor #4
AO 79 53 40080
DTC5 Discharge
Temperature
Discharge Temperature (Integer Value with 1 implied decimal) -
Compressor #5
AO 80 54 40081
DTC6 Discharge
Temperature
Discharge Temperature (Integer Value with 1 implied decimal) -
Compressor #6
AO 81 55 40082
General Alarm Reset
Chiller General Alarm Reset (Send 1 to reset)
AO 83 56 40084
General Alarm
Chiller General Alarm (1 - New Alarm Exists)
AO 84 57 40085
Actual SP
Chiller Actual Setpoint (Integer Value with 1 implied decimal)
AO 85 58 40086
Ambient
Temperature
Outside Air Temperature
AO 86 59 40087
Condenser Fan
Speed
Fan Speed Control %
AO 87 60 40088
Chiller Flow Chiller Flow Rate AO 89 61 40090
Chiller Pump Speed Chiller Pump Speed
AO 90 62 40091
Pump DP Pump Differential Pressure
AO 92 63 40093
FreeCool Valve
FreeCooling Valve Position
AO 93 64 40094
Fan Bank 1 State Fan Bank 1 Fan State AO 94 65 40095
Fan Bank 2 State Fan Bank 2 Fan State AO 95 66 40096
Fan Bank 3 State Fan Bank 3 Fan State AO 96 67 40097
Fan Bank 4 State Fan Bank 4 Fan State AO 97 68 40098
Average SDT Average SDT Temperature
AO 98 69 40099
FreeCool Fan Speed Free Cooling Fan Speed
AO 99 70 40100