RLC-SVU007E-GB
10
4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m
3
/h) 490 980 1400 1800 2700
nominal (m
3
/h) 820 1650 2300 3000 4500
maximum (m
3
/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
Ice Making (Optional)
Ice Making Command
This is the command to enter ice making. This setting is defined as an Auto/On settings. Setting this to On will
command the application into ice building if ice building is enabled and the Chiller is in the Auto” command mode.
Setting the Ice Making command to Auto will command the application to follow the next priority functional mode.
Regardless of the setting of the Setpoint Source (see setpoint arbitration.doc) any of the following 4 signals can
combine to comprise the Ice Building Command (assuming they are each installed).
Contact closure input for External Ice Making Command Front Panel Ice Making Command (also writable from TU
Lontalk Communicated Ice Making Command (LCI-C, BACnet, Modbus)
Time of Day scheduler
All ice making signals have to be turned to “auto” to be able to turn back Ice Making Command to “Auto” mode.
The overall Ice Making Command, must be toggled from “Ice Making”, to Auto” to “Ice Making” again, before Ice
Making can be entered a second time.
Ice Making Enable/Disable setting
This setting does not start or stop ice building. This is the command to enable or disable the entire ice building
feature. It can only be set through the Display or TU. The Ice Making Command starts and stops ice building.
Ice Making Termination setpoint
This setpoint controls when Ice Making is complete. If the Entering Water Temperature decreases below this setpoint
with no deadband Ice Making will be deemed complete. This setpoint has a range of –6.7°C (20°F) to 0°C (32°F) with
a default of -2.8°C (27°F).
Evaporator Application defines controls settings: if ICE is selected, Ice making is enabled. Specific hardware is
required for ice making command input and ice making status relay output.
UC800 provides auxiliary control thanks to Ice Making Status Relay. The normally open contact will be closed when
ice making is in progress and open when ice making has been normally terminated either through Ice Termination
setpoint being reached or removal of the Ice Making command. This relay inform customer equipment with chiller
mode changes from “ice making” to “ice complete”.
When contact is provided, the chiller will run normally when the contact is open.
UC800 will accept either an isolated contact closure (External Ice Making command) or a Remote Communicated
input (Tracer) to initiate and command the Ice Making mode.
UC800 also provides a “Front Panel Ice Termination Setpoint”, settable through Tracer™ TU, and adjustable from 20 to
31°F (-6.7 to -0.5°C) in at least 1°F (1°C) increments.
Note:
When the unit runs in Ice Making mode, and the evaporator entering water temperature drops below the ice
termination setpoint, the chiller terminates the Ice Making mode and changes to the Ice Making Complete Mode.
NOTICE:
Equipment Damage!
Freeze inhibitor must be adequate for leaving water temperature unless system components can be damaged.
Tracer™ TU must also be used to enable or disable Ice Machine Control. This setting does not prevent the Tracer from
commanding Ice Making mode. Upon contact closure, the UC800 will initiate an ice making mode, in which the unit
runs fully loaded at all times. Ice making shall be terminated either by opening the contact or based on the entering
evaporator water temperature. UC800 will not permit the ice making mode to be entered again until the unit has
been switched out of ice making mode.
If, while in ice making mode, the unit gets down to the freeze stat setting (water or refrigerant), the unit will shut
down on a manually resettable diagnostic, just as in normal operation.
Connect leads to the proper terminals. Refer to the field diagrams which are shipped with the unit. This customer
supplied contacts must be compatible with 24 VDC, 12 mA resistive load.

Other manuals for Trane Tracer TD7