RLC-SVU007E-GB
18
4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m
3
/h) 490 980 1400 1800 2700
nominal (m
3
/h) 820 1650 2300 3000 4500
maximum (m
3
/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
Smart Communication Protocol
LonTalk™ Interface (LCI-C)
UC800 provides an optional LonTalk™ Smart Com Protocol (LCI-C) between the chiller and a Building Automation
System (BAS). An LCI-C LLID shall be used to provide “gateway” functionality between a LonTalk compatible device
and the Chiller. The inputs/outputs include both mandatory and optional network variables as established by the
LonMark Functional Chiller Profile 8040. See integration guide for detailed information.
BACnet Interface (BCNT)
The Building Automation and Control Network (BACnet and ANSI/ASHRAE Standard 135-2004) protocol is a standard
that allows building automation systems or components from different manufacturers to share information and
control functions. BACnet provides building owners the capability to connect various types of building control
systems or subsystems together for a variety of reasons. In addition, multiple vendors can use this protocol
to share information for monitoring and supervisory control between systems and devices in a multi-vendor
interconnected system. The BACnet interface identifies standard objects (data points) called BACnet objects. Each
object has a defined list of properties that provide information about that object. BACnet also defines a number of
standard application services that are used to access data and manipulate these objects and provides a client/server
communication between devices. See integration guide for detailed information.
BACnet Testing Laboratory (BTL) Certification
All Tracer™ UC800 controllers are designed to support BACnet Smart Com Protocol. In addition, some particular
revisions of the UC800 firmware have been tested and have achieved BTL certification by an official BACnet testing
laboratory.
For more details, refer to the BTL website at www.bacnetassociation.org.
ModBus RTU Interface
Modicon Communication Bus (Modbus) is an application layer-messaging protocol that, like BACnet, provides
client/server communication between devices over a variety of networks. During communications on a Modbus RTU
network, the protocol determines how each controller will know its device address, recognize a message addressed
to its device, determine what action to take, and extract any data or other information contained in the message.
Controllers communicate using a master/slave technique, whereby, only one device (master) can initiate transactions
(queries). Other devices (slaves) respond by supplying the requested data to the master or by taking the action
requested in the query.
The master can address individual slaves or it can initiate a broadcast message to all slaves. In turn, the slaves
respond to queries that are addressed to them individually or broadcasted. The Modbus RTU Interface establishes
the format for the masters query by placing into it the device address, a function code defining the requested action,
any data to be sent, and an error-checking field. See integration guide for detailed information.

Other manuals for Trane Tracer TD7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Tracer TD7 and is the answer not in the manual?

Trane Tracer TD7 Specifications

General IconGeneral
BrandTrane
ModelTracer TD7
CategoryController
LanguageEnglish

Related product manuals