BAS-SVX48H-EN
Table 2. Connections (continued)
Connection
Quantity Types Range
Notes
Analog output/
binary input
(AO1/BI4 and
AO2/BI5)
2
Linear output 0–20 mA
Each termination must be configured as either an analog output
or binary input.
Linear output
0–10 Vdc
Binary input Dry contact
PWM output 80 Hz signal @ 15 Vdc
Pressure inputs
(PI1 and PI2)
2
3-wire 0–5 in H
2
O
• UC400: Pressure inputs supplied with 5 volts of power.
Designed for Kavlico™ pressure transducers.
• UC400–B: Used as a binary input for condensate on WSHP.
Overall Point
Total
23
(a)
Do Not mix Class 1 and Class 2 voltage wiring in an enclosure or on a controller without an approved barrier between the wiring.