EasyManua.ls Logo

Trane Tracer UC400 - Settings for CO2-Based Demand Controlled Ventilation; Calculating OA Damper and CO2 Setpoints

Trane Tracer UC400
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BAS-SVX48H-EN
63
Settings for CO
2
-Based Demand Controlled Ventilation
The CO
2
-based DCV sequence used in UC400 Controller is based on the sequence suggested in
the ASHRAE Standard 62.1 User Manual, Appendix A.
NNoottee:: This sequence is intended for a fan-coil, blower-coil, and unit ventilator product that is
applied as a single-zone ventilation system. That is to say, outdoor air enters through an
intake and is delivered to a single ventilation zone, which would be typical of a terminal
unit that is equipped with its own OA damper.
The following describes how to determine the appropriate OA damper and CO
2
setpoints for this
DCV sequence:
Calculate the required outdoor airflow (V
ot-Design
) at design occupancy using Equations 6-1, 6-
2- and 6-3 from ASHRAE Standard 62.1
V
bz
= R
p
× P
z
+ R
a
× A
z
(Equation 6-1)
V
oz
= V
bz
/ E
z
(Equation 6-2)
V
ot
= V
oz
(Equation 6-3, for single-zone ventilation systems), where
V
bz
= minimum outdoor airflow required in the breathing zone, cfm
R
p
= outdoor airflow required per person (from Table 6-1 in ASHRAE Standard 62.1), cfm/
person
R
a
= outdoor airflow required per unit of floor area (from Table 6-1 in ASHRAE Standard 62.1),
cfm/ft2
P
z
= zone population, number of people
A
z
= zone floor area, ft
2
V
oz
= zone outdoor airflow required, cfm
E
z
= zone air distribution effectiveness (from Table 6-2 in ASHRAE Standard 62.1)
V
ot
= outdoor air intake flow required, cfm
EExxaammppllee:: Consider an example K-12 classroom with a design population (P
z
) of 35 people
and a floor area (A
z
) of 1000 ft2. Table 6-1 in ASHRAE Standard 62.1-2010 requires 10 cfm of
outdoor air per person (R
p
) plus 0.12 cfm of outdoor air per square foot of floor area (R
a
) for
this type of space. The zone air-distribution effectiveness (from Table 6-2in Standard 62.1) is
determined to be 1.0 for this system configuration.
V
bz-Design
= 10 cfm/p x 35 people + 0.12 cfm/ft
2
x 1000 ft
2
= 470 cfm
V
oz-Design
= 470 cfm / 1.0 = 470 cfm
V
ot-Design
= 470 cfm
Use the same equations to calculate the required outdoor airflow (V
ot-DCVmin
) if no occupants
are currently present in the zone (P
z
= 0).
NNoottee:: This setpoint may need to be increased if the zone requires makeup air to replace air
that is exhausted directly from the zone (for example in a kitchen, a laboratory, an art
or science classroom, or any space with a restroom connected to it). In this case, the
V
ot-DCVmin
setpoint may need to be adjusted so that it is slightly above the local exhaust
airflow to ensure positive building pressurization.
EExxaammppllee::
V
bz-DCVmin
= 10 cfm/p x 0 people + 0.12 cfm/ft
2
x 1000 ft
2
= 120 cfm
V
oz-DCVmin
= 120 cfm / 1.0 = 120 cfm
V
ot-DCVmin
= 120 cfm
Use Equation A-J from the ASHRAE Standard 62.1-2010 User's Manual to calculate the
steady-state indoor CO
2
concentration (CO
2
space-Design
) when the zone is fully occupied and at
its design outdoor airflow rate (V
bz-Design
).
CO
2space
= CO
2outdoors
+ [1,000,000 x N / (V
bz
/ P
z
)] (rearrangement of Equation A-J) where,
CO
2space
= concentration of CO
2
in the breathing zone, ppm

Table of Contents

Other manuals for Trane Tracer UC400

Related product manuals