EasyManua.ls Logo

Trane Tracer ZN510 - Analog Inputs and Setpoint Functions

Trane Tracer ZN510
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12
Unit Operation
12 456 73
Analog Inputs
The ZN510 controller has five
available analog inputs (AI). These
inputs are factory-configured for the
following functions:
z Zone = Space temperature.
z Set = Local setpoint.
z Fan = Fan mode input.
z AI 1 = Leaving water tem-
perature (Circuit 1).
z AI 2 = Discharge air tem-
perature.
See Figure 8 for analog inputs.
Figure 7: High and low pressure switch
Note:
The ZN510 controller includes an automatic diag-
nostic reset function that allows the controller to
automatically recover after a high or low pres-
sure cutout diagnostic. After 30 minutes the con-
troller will reset the diagnostics. Most
diagnostics occur due to intermittent water tem-
perature or flow problem. The “smart reset” may
eliminate many service calls.
J3-4
AI 2
J3-3
J3-2
AI 1
J3-1
TB3-5
TB3-4
TB3-3
TB3-2
TB3-1
Discharge Air
Sensor
Leaving Water
Sensor (Circuit)
Zone
Setpoint
Fan
Analog Inputs
Zone Sensor
Figure 8: Analog inputs.
(1TB1-1)
Ground
(1TB1-2)
(1TB1-3)
(1TB1-4)
Binary Outputs
24 VAC
HPC LPC
Compr 2
Compr 1

Related product manuals