31
5 1/2”
4”
Heat sink is mounted to the top
of the control box
Hardware
Specifications
Specifications
Operating Environment
32 to 140 F (0 to 60 C)
5 to 95% non-condensing
Storage Environment
-40 to 185 F (-40 to 85 C)
5 to 95% non-condensing
Power Requirements
18 to 32 VAC (24 VAC nominal)
50 or 60 Hz
300 mA
Agency Listings
UL and CUL 916 Energy
Management System
Agency Compliance
IEC 1000-4-2 (ESD), IEC 1000-4-4
(EFT), IEC 1000-4-5 (Surge), FCC Part
15, Class A.
Input/Output Summary
z Three binary inputs.
z Six binary outputs only five are
used.
z Five analog inputs.
z Timed override ON and CANCEL.
z Comm5 communication.
Board Dimensions
Height: 4” (102 mm)
Width: 5-1/2” (140 mm)
Depth: 2-1/4” (57mm)
Figure 10: ZN510 Circuit Board