Termination module post-installation checklist
BMTK-SVN01D-EN 71
®
Table 19. Thermistor sensor electrical characteristics
Temperature (ºF) Temperature (ºC)
Sensor resistance
(ohms x 1000)
–30 –34 241.1
–20 –29 170.1
–10 –23 121.4
0–18 87.6
10 12 63.8
20 –7 46.9
30 –1 34.5
40 4 26.2
50 10 20.0
60 16 15.3
70 21 11.9
77 25 10.0
80 27 9.3
90 32 7.3
100 38 5.8
110 43 4 . 7
120 49 3.8
130 54 3.0
140 60 2.5
150 66 2.0

Table of Contents