EasyManua.ls Logo

Trane TSC060ED - Space Temperature Averaging

Trane TSC060ED
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
24 RT-SVX37B-EN
Controls using DC Analog Input/Outputs
(Standard Low Voltage Multi conductor
Wire)
Before installing any connecting wiring between the unit
and components utilizing a DC analog input\output signal,
refer to “Unit Dimensions,” p. 11 for the electrical access
locations provided on the unit.
Table 4 lists the conductor sizing guidelines that must
be followed when interconnecting the DC binary
output devices and the system components utilizing a
DC analog input\output signal to the unit.
Note: Resistance in excess of 2.5 ohms per conductor can
cause deviations in the accuracy of the controls.
Note: Ensure that the wiring between controls and the
unit’s termination point does not exceed two and a
half (2.5) ohms/conductor for the length of the run.
Do not run the electrical wires transporting DC signals
in or around conduit housing high voltage wires.
Route low voltage wiring per Figure 26, p. 24.
Space Temperature Averaging
Space temperature averaging is accomplished by wiring a
number of remote sensors in a series/parallel circuit.
Using the BAYSENS016* or BAYSENS077*, at least four
sensors are required to accomplish space temperature
averaging.
Example #1 in Figure 28, p. 26 illustrates two series
circuits with two sensors in each circuit wired in parallel.
The square of any number of remote sensors is required.
Example #2 Figure 28, p. 26 illustrates three sensors
squared in a series/parallel circuit. Using BAYSENS077*,
two sensors are required to accomplish space
temperature averaging.
Table 4. Zone Sensor Module wiring
Distance from Unit
to Control
Recommended
Wire Size
0 - 150 feet 22 gauge
0 - 45.7 m .33 mm2
151 - 240 feet 20 gauge
46 - 73.1 m .50 mm2
241 -385 feet 18 gauge
73.5 - 117.3 m .75 mm2
386 - 610 feet 16 gauge
117.7 - 185.9 m 1.3 mm2
611 - 970 feet 14 gauge
186.2 - 295.7 m 2.0 mm2
Figure 25. ReliaTel conventional thermostat field wiring
diagrams
RTRM
Figure 26. ReliaTel control customer low voltage
routing
Figure 27. ReliaTel options module

Related product manuals