XL 1050
18-HD80D1-6E-EN 13
5.3.6 Group 5* - Comfort Settings
* If Zoning is enabled, this group will be called Group 6.
MENU ITEM OPTIONS [DEFAULT] DESCRIPTION
Enable Dehumidification [Enable], Disable Select if enhanced dehumidification features are enabled.
Dehumidification Overcooling Limit - Degrees ① [0°] - 3°F
Select the maximum amount of overcooling allowed when the
indoor humidity exceeds the cooling target humidity setpoint.
Smart Continuous Fan Enable, [Disable] Select to enable or disable Smart Continuous Fan.
Control Response Rate [Normal], Fast Select the response rate of the control.
Aggressive Recovery ② > 2° Setpoint Change Enable, [Disable]
Select whether the 10-minute staging inhibit is disabled (heating or
cooling mode) with a setpoint change greater than 2°.
Heating Aggressive Recovery ② by Outdoor
Temperature
Enable, [Disable]
Select whether the 10-minute staging inhibit is disabled during
heating mode when the outdoor temperature falls below the
selected outdoor temperature (Outdoor temperature sensor must
be connected and enabled to allow this setting to be selected).
Heating Aggressive Recovery ②
Setting
0° - 70°F [40°F] Select the outdoor temperature for Heating Aggressive Recovery
Warm Air Discharge ① Enable, [Disable]
When enabled the indoor airflow will be limited to 80% on a call
for heat pump heating. This only applies to heat pump heating with
no call for aux heat (An indoor unit with a variable speed blower is
required).
① This feature is not available when zoning is enabled
② Only one method of recovery can be enabled.
Refer to Section 7 Advanced Operation for additional information on each setting.