Trouble Shooting
42 RT-SVX38B-EN
10 Flashes:ROM Fault
11 Flashes:EEPROM Fault
Heating Failure
Verify Heat Failure by Ignition Module (IGN) LED indicator:
OFF: No Power or Failure
ON:Normal
Slow Flash: Normal, Heat Call
Fast Flash:Error Code:
1 Flash:No Communication
2 Flashes:System Lockout
3 Flashes:Pressure Switch Fail
4 FlashesTC01 orTC02 Open
5 Flashes:Flame w/o Gas Valve
6 Flashes:Flame Rollout Open
Cooling Failure
Cooling and heating set point (slide pot) on the
thermostat has failed.
CC1 or CC2 24 VAC control circuit has opened, check
CC1 & CC2 coils, and any of the controls below that
apply to the unit (HPC1, HPC2, LPC1, LPC2, Frostat™).
Resetting Cooling and Ignition
Lockouts
Cooling Failures and Ignition Lockouts are reset in an
identical manner. Method 1 explains resetting the system
from the space; Method 2 explains resetting the system at
the unit.
Method 1
To reset the system from the space, turn the “Mode”
selection switch at the thermostat to the Off position.
After approximately 30 seconds, turn the “Mode”
selection switch to the desired mode, i.e. Heat, Cool or
Auto.
Method 2
To reset the system at the unit, cycle the unit power by
turning the disconnect switch Off and then On”.