SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing
of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury. When working on the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.
Packaged Rooftop Air Conditioners
Precedent™ Gas/Electric
3to10Tons–60Hz
Installation, Operation,
and Maintenance
Model Numbers
YSC037E - YSC067E YHC037E - YHC067E
YSC036E - YSC060E YHC036E - YHC072E
YSC072F - YSC120F YHC120E
YHC048F - YHC060F YHC072F - YHC102F
RT-SVX21P-EN
July 2014

Table of Contents

Other manuals for Trane YSC072F

Question and Answer IconNeed help?

Do you have a question about the Trane YSC072F and is the answer not in the manual?

Trane YSC072F Specifications

General IconGeneral
BrandTrane
ModelYSC072F
CategoryAir Conditioner
LanguageEnglish

Summary

Introduction

Warnings, Cautions, and Notices

Defines and explains the three types of safety advisories: WARNING, CAUTION, and NOTICE.

Copyright

Trademarks

Revision History

Model Number Description

Model Number Notes

Provides important context and clarifications for understanding the unit model number designations.

Model Number Description - 17 Plus

General Information

Unit Inspection

Details crucial steps for inspecting the unit upon arrival for shipping damage and verifying nameplate data.

Storage

Provides precautions to prevent condensate formation inside the unit during storage.

Unit Nameplate

Describes the information found on the unit's nameplate, including model, serial, and electrical data.

Compressor Nameplate

Indicates the location of the compressor nameplate on the side of the compressor.

Microchannel Condenser Barcode ID

Explains the purpose of the barcode decal for condenser coil part identification.

Unit Description

Provides an overview of the unit's factory testing and available control systems.

Economizer Control Actuator (Optional)

Details the function and operation of the optional economizer control actuator.

General Information

RTCI - Relia Tel™ Trane Communication Interface (Optional)

Describes the ReliaTel™ interface module for ICS building management systems.

RLCI - Relia Tel™ LonTalk Communication Interface (Optional)

Details the ReliaTel™ interface module for LonTalk building management systems.

RBCI - Relia Tel™ BACnet Communications Interface (Optional)

Explains the ReliaTel™ interface module for open BACnet protocol systems.

RTOM - Relia Tel™ Options Module

Describes the RTOM module for monitoring supply fan, filters, temperature, and other functions.

System Input Devices & Functions

Details basic input devices and their functions within the RTRM network.

General Information

Compressor Disable (CPR1/2)

Explains the low-pressure control input that disables compressor operation.

Low Pressure Control

Describes how the low-pressure control affects compressor operation and lockout.

High Pressure Control

Details how the high-pressure control impacts compressor operation and lockout.

Power Exhaust Control (Optional)

Explains the operation of the optional power exhaust fan.

Lead/Lag Control (Dual Circuit Only)

Describes the lead/lag control for dual circuit compressors.

Zone Sensor Module (ZSM)

Details the features and capabilities of the Zone Sensor Module (ZSM).

Wall Mounted Relative Humidity Sensor (BAYSENS036*)

Explains the use of the wall-mounted humidity sensor for dehumidification options.

General Information

Duct Mounted Relative Humidity Sensor (BAYSENS037*)

Describes the duct-mounted humidity sensor for dehumidification and reheat options.

Programmable Zone Sensor - (BAYSENS119*)

Details the 7-day programmable sensor with scheduling and dual temperature settings.

Remote Zone Sensor

Explains the function of remote zone sensors for temperature sensing.

Wireless Zone Sensor (BAYSENS050*)

Describes the wireless zone sensor with multiple system and fan settings.

High Temperature Sensor (BAYFRST001*)

Details the high-temperature sensor for emergency stop input and high-limit shutdown.

Evaporator Frost Control

Explains the evaporator frost control (FOS) and its activation methods.

General Information

Discharge Line Temp Switch (DLTS)

Explains the DLTS function in preventing compressor overheating during fan failures.

Smoke Detector Sensor (Optional)

Describes the optional smoke detector for detecting smoke in air streams.

Phase Monitor

Details the phase monitor for verifying 3-phase power supply and detecting imbalances.

Single Zone Variable Air Volume / Displacement Ventilation (Optional)

Explains the optional sensor for supply fan modulation and discharge air temperature control.

Human Interface - 5 Inch Color Touchscreen (Optional)

Describes the intuitive touchscreen interface for commissioning and troubleshooting.

Unit Dimensions

Installation

Pre-Installation

Covers essential pre-installation steps and safety precautions, including fiberglass wool handling.

Procedure

Details critical procedures for handling heavy objects and lifting the unit safely.

Installation

Foundation

Provides guidance on constructing proper foundations and footings for unit installation.

Horizontal Units

Specific foundation requirements for horizontal unit installations.

Ductwork

Roof Curb

Downflow

Details the downflow configuration for roof curb installation and verification.

Rigging

General Unit Requirements

Temperature Limit Switch Usage for Gas Heat Units

Horizontal Discharge Conversion (3 to 5 Ton Units)

TCO-1 Instructions

Horizontal Discharge Conversion (6 to 10 Ton Units)

TCO1 Instructions

Return Air Smoke Detector

Main Electrical Power Requirements

Through-the-Base Gas Installation

Requirements for Gas Heat

Outlines gas train and through-the-base gas shut-off valve pressure requirements.

Condensate Drain Configuration

Condensate Trap Installation

Provides guidelines for installing a condensate trap for proper drainage.

Drain Pan Removal (Units with Condensate Overflow Switch Option)

Details the procedure for removing the drain pan, noting switch wire disconnection.

Filter Installation

Field Installed Power Wiring

Main Unit Power

Standard Wiring

Explains standard unit power wiring connections at the compressor contactor.

Optional TBUE Wiring (Through-the-Base Electrical Option)

Details wiring for the optional Through-the-Base Electrical option.

Field-Installed Control Wiring

Control Power Transformer

Describes the 24-volt control power transformers and their circuit breakers.

Controls Using 24 VAC

Provides guidelines for connecting 24 VAC controls, including wire sizing and routing.

Controls using DC Analog Input/Outputs (Standard Low Voltage Multi conductor Wire)

Details wiring guidelines for DC analog input/output signals and wire sizing.

DC Conductors

Space Temperature Averaging (Relia Tel™ Only)

Pre-Start

Voltage Imbalance

Explains the importance of checking for and correcting excessive three-phase voltage imbalance.

Electrical Phasing (Three Phase Motors)

Details how to verify and correct electrical phasing for three-phase motors.

Pre-Start

Compressor Crankcase Heaters (Optional)

Explains the function and importance of optional compressor crankcase heaters.

ReliaTel™ Controls

Describes the ReliaTel™ control system's self-diagnostic checks and test procedures.

Pre-Start

Test Modes

Outlines the three methods for cycling through unit test modes.

ReliaTel™ Controls

Explains ReliaTel™ control system's self-diagnostics and initialization.

Electromechanical Controls Test Procedure

Unit Start-Up

Verifying Proper Air Flow

Details how to measure and verify proper airflow for unit performance.

Units with 5-Tap Direct Drive Indoor Fan

Explains airflow verification for units with 5-tap direct drive indoor fans.

Units with Belt Drive Indoor Fan

Describes airflow verification for units with belt drive indoor fans.

Unit Start-Up

Units with Direct Drive Indoor Fan - Electromechanical Control

Details airflow verification for electromechanical units with direct drive fans.

ReliaTel™ Units with Direct Drive Indoor Fan (7½ - 8½ Ton High Efficiency, 10 Ton Standard Efficiency)

Explains airflow verification for ReliaTel™ units with direct drive fans.

Unit Start-Up

Units with Constant CFM Direct Drive Indoor Fan

Details airflow verification for units with constant CFM direct drive indoor fans.

17 Plus units with the constant CFM direct drive indoor fan

Explains airflow adjustment procedure for 17 Plus units with constant CFM fans.

Variable Air Volume Applications (Traditional VAV)

Supply Air Temperature Control - Occupied Cooling and Heating

Describes supply air temperature control for occupied cooling and heating modes.

Supply Air Temperature Control with an Economizer

Explains economizer use for supply air temperature control, avoiding freeze-up.

VHR Relay Output

Details the VHR relay output operation for warm-up modes.

Zone Temperature Control without a Night Setback Panel or ICS - Unoccupied Cooling

Explains unoccupied cooling control without specific panels.

Zone Temperature Control without a Night Setback Panel or ICS - Unoccupied Heating

Describes unoccupied heating control without specific panels.

Morning Warm-up (MWU) Control

Details the MWU control sequence for bringing the space to occupied temperature.

Unit Start-Up

Daytime Warm-up (DWU) Control

Explains the DWU control function and its activation/deactivation settings.

Supply Duct Static Pressure Control

Describes the supply duct static pressure measurement and control.

Traditional VAV Standalone Operation

Details how to operate a traditional VAV unit without ICS, BAS, or front-end controllers.

Supply Air Temperature Reset

Explains how to reset supply air temperature based on outdoor or zone conditions.

Unit Start-Up

Economizer Start-Up

Provides steps for starting up the economizer, including safety warnings.

Minimum Position Setting for 17 Plus, 7.5-10 Ton with Multi-Speed, or Single Zone VAV

Details how to set the minimum damper position for ventilation.

Unit Start-Up

Compressor Start-Up

Guides through the process of starting up compressors, including rotation checks and pressure monitoring.

Dehumidification Option

Explains the operation of the dehumidification option during startup.

Gas Heat Units

Provides startup instructions for units with gas heat functionality.

Unit Start-Up

Final System Setup

Outlines final checks and programming for the unit before leaving the site.

Maintenance

Fan Belt Adjustment - Belt Drive Units

Details the procedure for adjusting and setting fan belt tension.

Maintenance

Monthly Maintenance

Covers routine monthly checks for filters, detectors, coils, and system pressures.

Filters

Instructions for inspecting, cleaning, or replacing return air filters.

Return Air Smoke Detector Maintenance

Explains periodic checks and maintenance for the return air smoke detector.

Condensate Overflow Switch

Details checking the condensate overflow switch float for free movement.

Cooling Season

Lists maintenance tasks specific to the cooling season.

Heating Season

Lists maintenance tasks specific to the heating season.

Maintenance

Coil Cleaning

Provides instructions for cleaning evaporator and condenser coils.

Hail Guard Removal

Details the steps for removing hail guards for coil access.

Microchannel (MCHE) Coils

Offers specific cleaning recommendations and warnings for microchannel coils.

Round Tube Plate Fin (RTPF) Coils

Explains the cleaning procedure for round tube plate fin coils using brushes and sprayers.

Annual Maintenance

Final Process

Guides on recording unit data for future reference and system checks.

Troubleshooting

ReliaTel™ Control

Provides steps to check ReliaTel™ control system diagnostics and status information.

System Status Checkout Procedure

Explains how to check system status using zone sensor LEDs or voltage readings.

Method 1

Details Method 1 for resetting cooling and ignition lockouts from the space.

Troubleshooting

Method 2

Details Method 2 for resetting cooling and ignition lockouts at the unit.

Service Failure

Lists potential causes and checks for service failures, including fan issues.

Simultaneous Heat and Cool Failure

Identifies potential causes for simultaneous heating and cooling failures.

System Failure

Explains how to check for system failure via voltage readings.

Heating Failure

Guides on diagnosing heating failures using the Ignition Module LED indicator.

Cooling Failure

Lists potential causes for cooling failures, such as thermostat or control circuit issues.

Troubleshooting

Zone Temperature Sensor (ZTS) Service Indicator

Explains the ZSM SERVICE LED and its indicators for filter or fan failure.

Clogged Filter Switch

Describes the function of the clogged filter switch and its LED indicator.

Resetting Cooling and Ignition Lockouts

Provides methods for resetting cooling and ignition lockouts.

Zone Temperature Sensor (ZTS) Tests

Details test procedures for zone temperature sensors and set points.

Test 1 - Zone Temperature Thermistor (ZTEMP)

Explains testing the ZTEMP thermistor by measuring resistance at different temperatures.

Test 2 - Cooling Set Point (CSP) and Heating Set Point (HSP)

Describes how to measure cooling and heating set point resistances for ZSM terminals.

Troubleshooting

Test 3 - System Mode and Fan Selection

Details measuring resistance for system mode and fan selection switch combinations.

Test 4 - LED Indicator Test, (SYS ON, HEAT, COOL & SERVICE)

Explains three methods to test unit LEDs using a meter.

Relative Humidity Sensor Test

Describes measuring the mA output signal of the relative humidity sensor for accuracy.

Programmable & Digital Zone Sensor Test

Covers testing serial communication voltage for programmable and digital zone sensors.

Relia Tel™ Refrigeration Module (RTRM) Default Chart

Explains RTRM default mode operation when input is lost.

Unit Operation without a Zone Sensor

Provides temporary operation instructions when a zone sensor is not used.

Troubleshooting

Unit Economizer Control (ECA) Troubleshooting

Guides through diagnosing ECA issues using test procedures and LED indicators.

Heating Failure

Details how to verify heating failure using the Ignition Module LED indicator.

Cooling Failure

Lists common causes for cooling failures, including thermostat and circuit issues.

Resetting Cooling and Ignition Lockouts

Explains identical methods for resetting cooling and ignition lockouts.

Method 1

Details Method 1 for resetting cooling and ignition lockouts from the space.

Troubleshooting

Unit Economizer Control (ECA) Test Procedures

Provides step-by-step tests for diagnosing ECA functionality and sensor inputs.

Electromechanical Control

Guides diagnostic tests for ECA with electromechanical controls.

Troubleshooting procedures for Direct Drive Plenum Fan

Outlines troubleshooting steps for direct drive plenum fans, including motor protection.

Unit Wiring Diagrams Numbers

Limited Warranty

Combination Gas Electric Air Conditioner YCC, YCD, YCH, YCP, YSC and YHC (Parts Only) Models Less Than 20 Tons for Residential Use*

Details limited warranty for residential use of Combination Gas Electric Air Conditioners.