Installation
RT-SVX21P-EN 41
Space Temperature Averaging
(ReliaTel™ Only)
Space temperature averaging is accomplished by wiring a
number of remote sensors in a series/parallel circuit.
Using the BAYSENS016* or BAYSENS077*, at least four
sensors are required to accomplish space temperature
averaging. See diagram below.
Example #1 illustrates two series circuits with two
sensors in each circuit wired in parallel.The square of
any number of remote sensors is required.
Example #2 illustrates three sensors squared in a
series/parallel circuit. Using BAYSENS077*, two
sensors are required to accomplish space temperature
averaging.
Example #3 illustrates the circuit required for this
sensor. Table 7, p. 43 lists the temperature versus
resistance coefficient for all sensors.
Note: Wiring pin numbers are for reference only. There
are multiple smoke detector systems that could
have differently numbered pins. For correct wiring
details, please refer to the specific smoke detector
literature that accompanied this unit.
Figure 51. Examples

Table of Contents

Other manuals for Trane YSC072F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane YSC072F and is the answer not in the manual?

Trane YSC072F Specifications

General IconGeneral
BrandTrane
ModelYSC072F
CategoryAir Conditioner
LanguageEnglish

Related product manuals