RT-SVX38B-EN 25
Note: Ensure that the wiring between controls and the
unit’s termination point does not exceed two and a
half (2.5) ohms/conductor for the length of the run.
Do not run the electrical wires transporting DC signals
in or around conduit housing high voltage wires.
Route low voltage wiring per Figure 27, p. 25.
DC Conductors
Space Temperature Averaging
(ReliaTel™ Only)
Space temperature averaging is accomplished by wiring a
number of remote sensors in a series/parallel circuit.
Using the BAYSENS016* or BAYSENS077*, at least four
sensors are required to accomplish space temperature
averaging. See diagram below.
Table 5. Zone sensor module wiring
Distance from Unit to Control Recommended Wire Size
0 - 150 feet 22 gauge
0 - 45.7 m .33 mm2
151 - 240 feet 20 gauge
46 - 73.1 m .50 mm2
241 -385 feet 18 gauge
73.5 - 117.3 m .75 mm2
386 - 610 feet 16 gauge
117.7 - 185.9 m 1.3 mm2
611 - 970 feet 14 gauge
186.2 - 295.7 m 2.0 mm2
Figure 25. ReliaTel conventional thermostat field wiring
diagrams
RTRM
Figure 26. ReliaTel options module
Figure 27. ReliaTel control customer low voltage
routing

Table of Contents