-33-
APD The amount of time, in seconds, that a visual alarm text will be displayed.
ATD Alarm temperature delay.
AAS Allows the customer to set the type of audible alarm style, either Blast, OFF or
Continuous.
CL Allows the customer to set the time of day.
DAY Allows the customer to set the date.
DS Sets daylight savings time On or OFF.
DL1 Selects the time to start a defrost lockout.
DL2 Selects the time to start a defrost lockout.
DL3 Selects the time to start a defrost lockout.
DL4 Selects the time to start a defrost lockout.
DCF Allows the customer to set the percentage of time that the door perimeter heaters
will operate, to control surface condensation.
CON The amount of time the compressor will run in the event of a cabinet air sensor
failure.
COF The amount of time, in minutes, that the compressor will be OFF in the event of a
cabinet air sensor failure.
EL Displays the evaporator temperature at the time (press set or the up arrow button
to display this feature).
DL Displays the discharge line temperature at the time (press set or the up arrow
button to display this feature).
CB When activated (by pressing the set or up arrow buttons), will display the cabinet
air temperature at the time the button is pressed.
PLn When activated will display the approximate line voltage.
RCO Will energize the compressor relay for 10 seconds when activated.
RdF Will energize the heater relay for 10 seconds when activated.
RFA Will energize the blower relay for 10 seconds when activated.
RDH Will energize the door heater relay for 10 seconds when activated.
Pro Parameter used only when reflashing the program memory.
CEP When activated, will return all of the parameters to the initial factory settings.
REF Displays the revision level of the software loaded into memory.
VIII. CONTROL PARAMETERS
VIII. a - PARAMETER DESCRIPTIONS (continued):