-25-
VI. b- HIGH TEMPERATURE ALARM
Door(s) open
longer than 5
minutes?
Check compressor
for low refrigerant.
YES
NO
Close
door(s).
Excessive
amount of hot
product placed
in unit?
YES
NO
Reduce
volume of
hot product.
Is evaporator
coil frozen up?
1
YES
NO
Defrost
evaporator
coil.
IS OK
Check that sensor
probe(s) properly
connected.
YES
IS NOT OK
Add
refrigerant.
IS NOT OK
Connect
probe(s).
Replace
failed
sensor.
1= See procedure on page 9.