-29-
VI. f- SYSTEM LEAK ALARM
Does
discharge temp
rise 45°F within
5 min. of a refn.
cycle start?
N
O
YES
Add
refrigerant.
Check compressor
for low refrigerant.
IS OK
Check discharge
line sensor.
1
Replace
failed
sensor.
IS NOT OK
IS NOT OK
Are sensor
probes properly
connected?
YES
Check for disolocated
sensor probe(s).
YES
NO
Connect
Probes.
Relocate
probe(s) to
proper position.
1= See procedure on page 8.