CHAPTER 1 - PRE-INSTALLATION REQUIREMENTS
1.3.1 PVC and CPVC Vent and Combustion Air
Piping and Fittings
PVC Schedule 40 - ANSI/ASTM D1785
PVC-DWV - ANSI/ASTM D2665
CPVC Schedule 40 - ANSI/ASTM F441
1.3.2 PVC and CPVC Pipe Cement and Primer
PVC - ANSI/ASTM D2564
CPVC - ANSI/ASTM F493
For installations in Canada, all piping, fit-
tings and cement/primer material must be
certified and listed to ULC-S636. Ipex Inc. is
an approved manufacturer of ULC S636 vent
components.
Use of cellular core PVC (ASTM F891) cel-
lular core CPVC, or Radel® (polyphenol-
sulfone) in venting systems is prohibited.
Cellular core pipe may be used for combus-
tion air piping.
DO NOT mix a PVC/CPVC vent system & com-
ponents with other vent system materials &
components. Seal all PVC and CPVC pipe and
fittings with the appropriate primer and ce-
ment. Failure to comply with this requirement
can cause the venting system to fail resulting
in substantial property damage, serious injury,
or death.
NOTICE
WARNING
1.3.3 AL29-4C® Stainless Steel Vent Piping and
Fittings
Approved AL29-4C® Stainless Steel vent manufacturers
and vent systems:
SelKirk/Heatfab
DuraVent
Z-FLEX U.S. Inc.
Only use approved stainless steel vent adapters and
terminations listed in Table 1 on page 3.
Contact approved AL29-4C® stainless steel
vent manufacturer for a copy of their instal-
lation instructions. Read, understand and fol-
low all of the vent manufacturer’s instructions
before beginning the installation. Contact
vent manufacturer if you require any tech-
nical support. Failure to properly install and
support vent system can cause the venting
system to fail, resulting in substantial proper-
ty damage, serious injury, or death.
When using stainless steel for the vent system,
PVC or CPVC pipe meeting the listed require-
ments in this manual may be utilized for the
combustion air piping.
WARNING
NOTICE
Table 1 - Approved Stainless Steel Vent Adapters and Terminations
Description
SelKirk / Heatfab
Saf-T Vent EZ Seal or
Saf-T Vent SC
DuraVent
FasNSeal or CVS
Z-Flex U.S. Inc.
Z-Vent
3” Vent Adapter Not required Not required Not required
3” Roof & Side Wall Straight Termination 9392 300186 2SVSTPF03
3” Side Wall & 45° Elbow Termination 9311TERM 300130 & 300186 2SVSTEX0345
3” Side Wall Tee Termination 9390TEE 300311 2SVSTTF03

Table of Contents

Other manuals for TriangleTube Instinct Solo Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the TriangleTube Instinct Solo Series and is the answer not in the manual?

TriangleTube Instinct Solo Series Specifications

General IconGeneral
BrandTriangleTube
ModelInstinct Solo Series
CategoryBoiler
LanguageEnglish

Related product manuals