2 Inch Vent Pipe
PVC or CPVC
Material
2 Inch Vent Pipe
Min. 7 Feet Length
CPVC Material
3 x 2 Bell Reducer
CPVC Material
3 Inch Stub Vent Pipe
CPVC Material
2 Inch Vent Pipe
PVC or CPVC
Material
2 Inch Vent Pipe
CPVC Material
2 Inch 90º
Long Sweep Elbow
CPVC Material
3 x 2 Bell Reducer
CPVC Material
3 Inch Stub Vent Pipe
CPVC Material
29
CHAPTER 4
Fig. 21 - 2” CPVC/PVC Venting System Vertical
CHAPTER 4 - INSTALLATION REQUIREMENTS
4.1. Vent/Combustion Air Transitions
4.1.1 3” to 2” (60 mm) Transitions
This chapter outlines the installation of 2” (60
mm) Venting and Combustion Air Piping for
the INSTINCT units when the vent system must
transition from the 3” outlet of the boiler to the
2” (60 mm) vent system.
1. The transition from 3” vent system to 2” (60 mm)
vent system must occur at the boiler vent outlet.
2. The transition from 3” vent to 2” (60 mm) vent must
occur in a vertical run only.
Transition of 3” vent to 2” (60 mm) vent in a
horizontal run will result in pooling of the
condensate and potential vent blockage. Fail-
ure to transition from 3” vent to 2” (60 mm)
vent in a vertical run can result in substantial
property damage, serious injury, or death.
3. Use a 3” x 2” bell reducer to make the transition to
2” CPVC/PVC vent, see Figs. 21 and 22.
4. Use a 3” appliance vent adapter and 3” (80 mm) to 2”
(60 mm) reducer to make the transition to 2” (60 mm)
Polypropylene vent. See Table 2 on page 4.
5. The 2” (60 mm) vent must not transition back to 3”
(80 mm) vent at any point in the vent system.
6. The PVC combustion air piping shall transition from
3” to 2” using a 3” x 2” bell reducer and shall transition
in a similar manner as the vent system.
7. The total equivalent length of the 3” (80 mm) and
2” (60 mm) vent piping combined shall not exceed
the length listed for a 2” (60 mm) vent system in Ta-
ble 6 on page 7.
8. The total equivalent length of 3” (80 mm) and 2” (60
mm) combustion air piping combined shall not ex-
ceed the length listed for a 2” (60mm) combustion
air system in Table 6 on page 7.
NOTICE
WARNING
Fig. 22 - 2” CPVC/PVC Venting System Horizontal

Table of Contents

Other manuals for TriangleTube Instinct Solo Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the TriangleTube Instinct Solo Series and is the answer not in the manual?

TriangleTube Instinct Solo Series Specifications

General IconGeneral
BrandTriangleTube
ModelInstinct Solo Series
CategoryBoiler
LanguageEnglish

Related product manuals