EasyManuals Logo

Trinity ENTITY User Manual

Trinity ENTITY
13 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #5 background imageLoading...
Page #5 background image
TRINITY
[5]
Entity Operational Manual
Technical Specifications
Parameter
Type
Name
Statistics
INPUT
Supply
Three Phases and Neutral of a 3P4W system
Voltage
Direct Voltage Input : Up to 300V L-N or 500V L-L
Burden : 0.5VA
Current
Secondary Current Input : 5A or 1A (Site Selectable)
CT Primary : Site Selectable
Range of Reading : 5 5000A
Burden : < 1.0VA
Overload (Through CT) : 5A CT = 6A RMS Continuous
1A CT = 1.2A RMS Continuous
(Whole Current) : 120% of Imax continuous
Power Supply
Wide operating Voltage SMPS : 80 VAC - 270 VAC, 50-60 Hz.
MEASUR
EMENT
Total Active Energy
(KWh)
Range of Reading : 0 to 9999999.9 KWh
Accuracy : 1.0S as per IS13779.
Bezel
96 X 96 mm
Panel Cutout
92 X 92 mm
Depth of installation
55 mm
Display
16X1 LCD
Operating temp
10°C to 50°C
Min. Operating Current
0.4% OF CT-Secondary