CALIBRATE FLOW SUBMENU
PRESSURE FLOW STATION
FLOW STATION
PRESSURE ZERO
FHM10 and
FHC50
The FLO STA PRESS ZERO item is used to calibrate the
zero in the pressure transducer. See Calibration section for
the procedure to zero the flow station.
FLOW STATION
OUTPUT RANGE
FHM10 and FHC50
The FLO STA FS V item is used to set the voltage signal
output range of the pressure transducer. Set this item to
match the pressure transducer used.
NOTE: If a pressure transducer with a 1-5 V output is
used, select 0 to 5V. If a pressure transducer with a
2-10 V output is used, select 0 to 10V
FLOW STATION
LOW CAL
FHM10 and FHC50
The FLO STA LO CAL menu item enters the FLO STA LO
CAL Submenu.
FLOW STATION
HIGH CAL
FHM10 and
FHC50
The FLO STA HI CAL menu item enters the FLO STA HI
CAL Submenu.
FLOW K FACTOR
FHM10 and
FHC50
The K FACTOR menu item sets the āKā factor for the flow
signal. The flow signal is multiplied by the K FACTOR so
that the flow measurement matches the actual flow,
determined with a pitot tube traverse.
NOTE: FLOW K FACTOR modifies the entire range of the
calibrated flow, not just a single point.