ATS-800 Series Automatic Transfer Switches Rev. 3, April, 2018
TSi Power Corporation Proprietary Information 17
- For pluggable equipment, the socket-outlet shall be installed near the
equipment and shall be easily accessible.
- The ATS must be protected by an upstream branch circuit protector, for both
the Primary and the Backup, at 125% of the ATS current rating (the maximum
input current rating as shown on the ATS product label) per the National Electric
Code or per local electrical codes if outside of the United States.
CAUTION: THE UNIT MUST BE PLACED IN A WELL - VENTILATED AREA TO
PREVENT RISK OF FIRE DUE TO OVERHEATING. VENTILATION SLOTS MUST NOT
BE OBSTRUCTED.
Select an area with enough space to provide sufficient clearance around the unit
to provide unrestricted access.
3.2 REQUIRED TOOLS
Set of standard hand tools
Wire stripper (for hardwired units)
3.3 UNPACKING & INSPECTION
3.31 The units are shipped in individual cartons and may come stacked on wooden pallets
depending on the size of the order. In this configuration, the units are placed on the
pallet, with protective material between them.
3.32 Carefully open the cartons, making sure not to damage the units, and remove the
protective wrap and packing material.
3.33 Before the units are removed from the cartons, inspect them for physical damage.
3.34 If no damage is found, remove the units from the carton, open the top cover and again
inspect for damage. If damage is found in either steps 3.33 or 3.34, do not accept the
shipment and file a claim with the carrier. Contact TSi Power for assistance if necessary.
3.4 VOLTAGE SELECTION
3.41 If you have a 208, 220 or 240 V ATS the voltage selection can be changed. The factory
setting is either set to HIGH (220 to 240 V) or LOW (208 V) depending on what ATS
model was ordered. If the factory preset is not desired, performing the following steps will
change the voltage transfer points.
3.42 Make sure both Primary and Backup AC sources to the ATS are de-energized.
3.43 Remove the ATS case cover.