TSi Power Corporation MC80043,4,5,6,7,8,9,50
ATS-800 Series Automatic Transfer Switches Rev. 3, April, 2018
TSi Power Corporation Proprietary Information 23
Since a board exchange is the quickest way to repair an ATS Series failed circuit board,
TSI recommends that customers keep at least 3-5% (one board for every 20 or 30 ATS
units) in spare boards.
6. REFERENCE
6.1 SPECIFICATIONS
6.11 MC80043 ATS-800 SERIES HARDWIRE, 120 V, MODELS 800-2000, -4000, -6000 and
-8000
TSi P owers ongoing product improvement process m akes specifications subject to change. Other com panies product
nam es herein are for identification purposes only and m ay be trademarks of their respective com panies.
SP EC IFIC A TIO N
ATS-800-2000 ATS -800-4000 ATS-800-6000 ATS -800-8000
ELECTRICAL
VA at 120 V 1800 2400 3600 4800
Circuit breaker
15 A 20 A 30 A 40 A
Switching technology M echanical relays
INP U T
Voltage / Current / Voltage range 120 V / 15, 20, 30, 40 A (92 - 132 V)
Frequency range 47 to 63 H z, Caution: Both sources m ust use same nom inal frequency
Transfer tim e Typically ½ cycle (~8 ms for 60 H z or ~9.7 ms for 50 H z)
Input / output wire size 14 AW G (2.08 m m ²) 12 AW G (3.3 m m ²) 10 AW G (5.26 m m ²) 8 AW G (8.36 mm²)
AC input and output connections Hardw ire term inals
(standard H ardwired units m ust be installed by a qualified electrician)
OUTPU T
Voltage / Current 120 V / 15, 20, 30 or 40 A
Load regulation 1 % from no load to full load
Pow er efficiency 99 % or higher
AC distribution Hardw ire term inals
(standard H ardwired units m ust be installed by a qualified electrician)
LED indicators: Green: Prim ary output, Yellow : B ackup output, Red: N o prim ary or backup AC
Audible alarm B uzzer beeps w hen loss of prim ary or backup AC occurs
Audible alarm on / off Enable / Disable sw itch
Alarm contacts Rear-m ounted D B-9 connector sends loss of prim ary / backup AC
PH YSIC A L
Dim ensions: Inches / mm W : 16.63" / 422 mm H : 1.7" / 43 m m D : 10.5" / 267 mm
W eight: lbs / kg 8 lbs / 3.63 kg
Integral 19" Front Rack-M ount Standard
EN VIR ONMEN TAL
Am bient tem perature 32° to 104° F / 0° to 40° C
AG ENC Y APPRO VALS
Safety UL 60950-1 Issue: 2007/03/27 Ed:2 UL Standard for Safety Inform ation Technology Equipm ent - Safety
- Part 1: General Requirem ents - C SA C22.2#60950-1 Issued: 2007/03/01 Ed:2 Inform ation Technology
Equipm ent Safety Part 1: G eneral R equirem ents
W ARR ANTY
W arranty Two year lim ited warranty covers parts and labor