13
2018/10
Index 0x55: Measured value update time/rotating/disabling a display
Value (hexadecimal) Menu item Function
0x00 50 50 ms measured value update time
0x01 200 200 ms measured value update time
0x02 600 600 ms measured value update time
0x03 r50 50 ms measured value update time/display rotated 180°
0x04 r200 200 ms measured value update time/display rotated 180°
0x05 r600 600 ms measured value update time/display rotated 180°
0x06 Off Display disabled
Index 0x58: Menu locked
Value (hexadecimal) Function
0x00 Menu unlocked
0x01 Parameters can be displayed but not changed
(not even in SIO mode)
0x02 Menu generally locked
Index 0x59: IO-Link write protection
Value (hexadecimal) Function
0x00 No write protection
0x01 Writing of parameters via IO-Link not possible (except 0x59)
Index 0x60: Switch and reset point 1
Switch point (SP) and related reset point (rP) are transferred together as one record in process
value format. Transfer is executed according to the “big endian” specification.
Switch point Reset point
MSB LSB MSB LSB
0 1
The following values are allowed:
The switch point must be at least 0.5 % f.s. above the reset point:
SP - rP > 0x45
The reset point must be at least 0.5 % f.s. above the start value of the measuring range:
rP > 0x545
The switch point should not exceed the end value of the measuring range:
SP ≤ 0x3AFF
Index 0x61: Switch and reset point 2
See index 60: Switch and reset point 1