TFP610
Page 19 of 28
DRY SYSTEM SHOWN
RIDGE
OBSTRUCTION
DRY SYSTEM SHOWN
RIDGE
WALL OR
DRAFT CURTAIN
AT RIDGE
HIP
DRY SYSTEM SHOWN
RIDGE
WALL OR
DRAFT CURTAIN
AT RIDGE
WET SYSTEM SHOWN
HIP
HIP
HIP
HIP
FIGURE 20-A-3. BB AND SD SPRINKLERS
Wet Systems — Calculate the most de-
manding ve BB Sprinklers plus two SD
Sprinklers.
Dry Systems — Calculate the most de-
manding seven BB Sprinklers plus up to two
SD Sprinklers (see adjacent gure).
FIGURE 20-A-4. SD SPRINKLERS
• Wet Systems — Calculate the most de-
manding five SD Sprinklers.
• Dry Systems — Calculate the most de-
manding nine SD Sprinklers (see adja-
cent figure).
FIGURE 20-A-5. SD AND HIP SPRINKLERS
Wet Systems — Calculate the most de-
manding ve sprinklers.
Dry Systems — Calculate the most demand-
ing nine sprinklers with a maximum of seven
to be SD Sprinklers (see adjacent gure).
FIGURE 20-A-6. HIP SPRINKLERS
Wet Systems — Calculate the most de-
manding ve sprinklers (see adjacent g-
ure).
Dry Systems — Calculate the most de-
manding nine sprinklers.