TFP1410
Page 11 of 14
Installation
General Instructions
1-1/2 inch (DN40) risers utilize a 2 inch 
(DN50) Riser Check Valve in combina-
tion with the 1-1/2 inch (DN40) DV-5 
Deluge Valve.
Proper operation of the DV-5 Deluge 
Valves depends upon their trim being 
installed in accordance with the in-
structions given in this technical data 
sheet. Failure to follow the appropri-
ate trim diagram may prevent the DV-5 
Valve from functioning properly, as well 
as void listings, approvals, and the 
manufacturer’s warranties.
The DV-5 Valve must be installed in a 
readily visible and accessible location.
The DV-5 Valve, associated trim, and 
wet pilot lines must be maintained at 
a minimum temperature of 40°F (4°C).
Heat tracing of the DV-5 Valve or its 
associated trim is not permitted. Heat 
tracing can result in the formation of 
hardened mineral deposits that are ca-
pable of preventing proper operation.
The DV-5 Deluge Valve is to be in-
stalled in accordance with the follow-
ing criteria:
Step 1. All nipples, ttings, and de-
vices must be clean and free of scale 
and burrs before installation. Use pipe 
thread sealant sparingly on male pipe 
threads only.
Step 2. The DV-5 Valve must be 
trimmed in accordance with Figure 3A 
or 3B.
Step 3. Care must be taken to ensure 
that check valves, strainers, globe 
valves, etc. are installed with the ow 
arrows in the proper direction.
Step 4. Drain tubing to the Drip Funnel 
must be installed with smooth bends 
that will not restrict ow.
Step 5. The main drain and Drip Funnel 
drain may be interconnected provided 
a check valve is located at least 12 
inches (300 mm) below the Drip Funnel.
Step 6. Suitable provision must be 
made for disposal of drain water. Drain-
age water must be directed such that 
it will not cause accidental damage to 
property or danger to persons.
Step 7. Connect the Diaphragm Cham
-
ber Supply Control Valve to the inlet 
side of the system’s Main Control Valve 
in order to facilitate setting of the DV-5 
Valve (Ref. Figure 4).
Step 8. An Inspector’s Test Connec-
tion, as described in the Technical Data 
section, must be provided for Wet Pilot 
Actuation systems.
Step 9. Unused pressure alarm switch 
connections must be plugged.
Step 10. A suitable automatic supervi-
sory air (nitrogen) supply, as described 
in the Technical Data section, is to be 
installed in accordance with the appli-
cable technical data sheet and set for 
10 ± 2 psi (0,69 ± 0,14  bar).
Step 11. A desiccant dryer, when re-
quired for the supervisory air supply, is 
to be installed between a drip leg and 
the Model AMD-1 Air Maintenance De-
vice or between the Model G16AC812 
Automatic Supervisory Air Supply and 
the Preaction Trim.
Step 12. The Supervisory Low Pres-
sure Alarm Switch is to be wired to the 
supervisory alarm initiating circuit of an 
alarm panel.
Step 13. Conduit and electrical con-
nections are to be made in accordance 
with the requirements of the authority 
having jurisdiction and/or the National 
Electric Code.
Step 14. Before a system hydrostatic 
test is performed in accordance with 
NFPA 13 system acceptance test re-
quirements, the DV-5 Diaphragm 
Chamber is to be depressurized; the 
Automatic Drain Valve (Item 4, Fig. 3A) 
is to be temporarily replaced with a 1/2 
inch NPT plug, the 3/32 inch Vent Fit-
ting (Item 16 - Fig. 3A) is to be tem-
porarily replaced with a 1/4 inch NPT 
plug, and the Diaphragm Cover Bolts 
must be uniformly and securely tight-
ened using a cross-draw sequence. Af-
ter tightening, double- check to make 
certain that all of the Diaphragm Cover 
Bolts are securely tightened.
Valve Setting 
Procedure
Steps 1 through 12 are to be performed 
when initially setting the DV-5 Deluge 
Valve after an operational test of the 
re protection system, or after system 
operation due to a re.
Step 1. Close the Main Control Valve.
Step 2. Close the Diaphragm Chamber 
Supply Control Valve, and close the Air 
Supply Control Valve (Ref. Fig. 3B).
Step 3. Open the Main Drain Valve, 
System Drain Valve, and all auxiliary 
drains in the system. Close the System 
Drain Valve and auxiliary drain valves 
after water ceases to discharge. Leave 
the Main Drain Valve open.
Step 4. Depress the plunger of the Au-
tomatic Drain Valve to verify that it is 
open and that the DV-5 Valve is com-
pletely drained.
Step 5. Clean the Strainer  in the Dia-
phragm Chamber Supply connection 
by removing the clean-out plug and 
strainer basket. The Strainer may be 
ushed out by momentarily opening 
the Diaphragm Chamber Supply Con-
trol Valve.
Step 6. Reset the actuation system.
Manual Actuation — Push the op-
erating lever up; however, do not 
close the hinged cover at this time.
Wet Pilot Actuation — Replace op-
erated pilot sprinklers and/or reset 
the manual control stations.
NOTE: In order to prevent the possi-
bility of a subsequent operation of an  
over-heated solder type pilot sprinkler, 
any solder type pilot sprinklers that 
were possibly exposed to a tempera-
ture greater than their maximum rated 
ambient must be replaced.
Step 7. Open the Diaphragm Chamber 
Supply Control Valve and allow time 
for full pressure to build up in the Dia-
phragm Chamber.
Step 8. Operate (open) the Manu-
al Control Station to vent trapped air 
from the Diaphragm Chamber. If nec-
essary, rst open the hinged cover, and 
then fully pull down on the operating 
lever. Slowly close the operating lever 
by pushing it up after aerated water 
ceases to discharge from the Manual 
Control Station drain tubing. Close the 
hinged cover and insert a new break 
rod in the small hole through the top of 
the enclosing box.
Crack open the Inspector’s Test Con-
nection and any other vent valves on 
the wet pilot line to relieve trapped air. 
After the discharge of air has stopped, 
close the vent valves and the Inspec-
tor’s Test Connection
Step 9. Inspect the drain connections 
from the Manual Control Station. Any 
leaks must be corrected before pro-
ceeding to the next step.
Step 10. Verify the ability for the DV-5 
Diaphragm to hold pressure as follows:
• With the diaphragm chamber pres-
surized per Step 8, temporarily 
close the Diaphragm Chamber Sup-
ply Control Valve, and then monitor 
the Diaphragm Chamber Pressure 
Gauge for a drop in pressure.
• If a drop in pressure is noted, the 
DV-5 Diaphragm is to be replaced 
and/or any leaks must be corrected 
before proceeding to the next step.
• If the Diaphragm Chamber Pres-
sure Gauge indicates no drop in 
pressure, re-open the Diaphragm 
Chamber Supply Control Valve and 
proceed to the next step.
Step 11. Replace operated automatic 
sprinklers on the system piping and 
then open the Supervisory Air Supply 
Control Valve and allow the system to 
automatically re-establish its nominal