FASTFLEX Model YN25, YB25, and YB28 
Flexible Sprinkler Hose Assembly 
Europe, Middle East, and Africa Only
Worldwide 
Contacts
www.tyco-fire.com
Page 1 of 8  FEBRUARY 2016  TFP720
Technical 
Data
Approvals
UL Listed
FM Approved
VdS Approved
LPCB Approved
(Specific details for laboratory approvals 
are given in Table A, and the approvals 
apply to the service conditions indicated 
in the applicable Design Criteria sections)
APSAD accepted per Table A
CSTB accepted for all models and 
assembly lengths
Inlet Connections (Ref. Figure 1)
ISO 7-R 1 
ISO 7-R 1 1/4
Outlet Connections (Ref. Figure 2)
ISO 7-Rc 3/8 
1/2 inch NPT 
3/4 inch NPT
Nominal Assembly Lengths
Ref. Table A
Construction (Ref. Figure 1)
The Inlet Nipple is mild steel, and the 
Flexible Hose is SS AISI 304. The 
connection at each end of the Flexible 
Hose utilizes a brass Slip Nut, NBR/
CR o-ring, and Nylon W6 washer. The 
Sprinkler Reducer is mild steel. The 
Reducer Bracket, Bar Fixing Clamps, and 
Support Bar are pressed steel.
General 
Description
The TYCO FASTFLEX Flexible Sprinkler 
Hose is a unique sprinkler drop assem-
bly comprised of a branchline adapter 
nipple, stainless steel flexible hose 
with two slip nuts, sprinkler reducer, 
and lightweight ceiling bracket com-
ponents. (Ref. Figure 1.)
The FASTFLEX Flexible Sprinkler Hose 
can be installed in false ceilings without 
cutting and threading pipes associ-
ated with installing a drop, armover, 
and elbows. FASTFLEX makes it pos-
sible to test and charge the system with 
water before the ceiling grid is installed. 
Once the ceiling grid is in position, the 
FASTFLEX hoses can be reshaped to 
suit the final sprinkler location without 
draining the system.
FASTFLEX Flexible Sprinkler Hose 
is installed quickly without large and 
expensive tools. Ideal projects are 
offices, schools, libraries, hospitals, 
and shopping complexes. FASTFLEX 
sprinkler hoses are for use on wet pipe, 
preaction, and dry pipe systems. The 
FASTFLEX hose can also be used in 
conjunction with ultra-low flow water 
mist nozzles following the design crite-
ria outlined in this technical data sheet.
NOTICE
The FASTFLEX flexible sprinkler hoses 
described herein must be installed 
and maintained in compliance with 
this document and with the applicable 
standards recognized by the Approval 
agency, in addition to the standards of 
any other authorities having jurisdiction. 
Failure to do so may impair the perfor-
mance of these devices.
The owner is responsible for main-
taining their fire protection system 
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any 
questions.