5. Functional Specification
5.1 T1200 Panel Input/Output List
Input/Output
T1204
T1216-C
T1232-C
Detection zones
4
16
32
Remote silence alarm I/P [non monitored]
1
1
1
Remote reset I/P [non monitored]
1
1
1
Remote Manual Fire Alarm/Muster I/P [non monitored]
1
1
1
Class change I/P [non monitored]
1
1
1
Sounder circuits
4 @ 0.5A
4 @ 1A
4 @ 1A
Zonal O/Ps [open collector] 4
4 on Motherboard,
additional outputs via O/P
expansion system
Disablement active [open collector]
1
1
1
Manual Fire Alarm/Muster active [open collector] not
activated when panel microprocessor fails.
1 1 1
Buzzer active [open collector]
1
1
1
Monitored Fire Output
1
1
1
Monitored Fire Protection O/P
1
1
1
Monitored Fault Output
1
1
1
Volt-free Reset Relay
1
1
1
Aux DC Supply [fused]
1 @ 0.5A
1 @ 1A
1 @ 1A
Repeater facility
N/A
Optional
Optional
Remote Muster I/P [from repeater] via optional muster
interface
N/A Optional Optional
T1216-C & T1232-C only:
Voyage data recorder O/P module providing 1 x volt-
free changeover relay contact for each of the following
alarms:
Common Fire.
Machinery Space Fire.
Common Fault.
Mains Failed.
Battery Failed.
(All contacts rated 1A @ 30Vdc)
1xRS422 output also provided, conforming to
IEC 61162-1.
N/A 1 1
Additional Outputs via O/P expansion system
N/A
Optional
Optional